Carrier 38APD025-100 Air Conditioner User Manual


 
31
Table 9 — 38APS Standard Condenser Fan Electrical Data
Table 10 — 38APS Low Sound Condenser Fan Electrical Data
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to
the unit terminals is not below or above the listed minimum and maximum
limits. Maximum allowable phase imbalance is: voltage 2%; amps 10%.
2. All units or modules have single point primary power connection. Main
power must be supplied from a field-supplied disconnect.
3. For MCA that is less than or equal to 380 amps, 3 conductors are
required.
For MCA between 381 and 760 amps, 6 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C. Use copper conductors
only.
a. Incoming wire size range for terminal block with MCA up to 175 amps is
14 AWG (American Wire Gage) to 2/0.
b. Incoming wire size range for terminal block with MCA from 175.1 amps
to 420 amps is 2 AWG to 600 kcmil.
c. Incoming wire size range for non-fused disconnect with MCA up to
100 amps is 14 AWG to 1/0.
d. Incoming wire size range for non-fused disconnect with MCA from
100.1 amp to 200 amps is 6 AWG to 350 kcmil.
e. Incoming wire size range for non-fused disconnect with MCA from
200.1 amp to 450 amps is 3/0 to 500 kcmil.
38APS UNIT
SIZE
V-Ph-Hz
SUPPLY
VOLTAGE
COMPRESSOR CONDENSER FAN
MCA MOCP
REC
FUSE
ICF
Min Max Qty RLA LRA Total Qty FLA
025
208/230-3-60 187 254
2
48.1 245
2
6.6 121.4 150 150 306.3
380-3-60 342 418 23.7 145 3.9 61.1 80 70 176.5
460-3-60 414 506 18.6 125 3.3 48.5 60 60 150.2
575-3-60 518 632 14.7 100 2.6 38.3 50 45 119.9
380/415-3-50 342 440 18.6 118 3.3 48.5 60 60 143.2
027
208/230-3-60 187 254
2
51.3 300
2
6.6 128.6 175 150 364.5
380-3-60 342 418 26.9 139 3.9 68.3 90 80 173.7
460-3-60 414 506 23.1 150 3.3 58.6 80 70 179.7
575-3-60 518 632 19.9 109 2.6 50.0 60 60 134.1
380/415-3-50 342 440 23.1 140 3.3 58.6 80 70 169.7
030
208/230-3-60 187 254
2
55.8 340
2
6.6 138.8 175 175 409.0
380-3-60 342 418 34.0 196 3.9 84.3 110 100 237.8
460-3-60 414 506 26.9 179 3.3 67.1 90 80 212.5
575-3-60 518 632 23.7 132 2.6 58.5 80 70 160.9
380/415-3-50 342 440 26.9 174 3.3 67.1 90 80 207.5
040
208/230-3-60 187 254
3
51.3 300
3
6.6 186.5 225 200 422.4
380-3-60 342 418 26.9 139 3.9 99.1 125 110 204.5
460-3-60 414 506 23.1 150 3.3 85.0 100 100 206.1
575-3-60 518 632 19.9 109 2.6 72.5 90 80 156.6
380/415-3-50 342 440 23.1 140 3.3 85.0 100 100 196.1
050
208/230-3-60 187 254
3
55.8 340
3
6.6 201.2 250 225 471.4
380-3-60 342 418 34.0 196 3.9 122.2 150 150 275.7
460-3-60 414 506 26.9 179 3.3 97.3 110 110 242.7
575-3-60 518 632 23.7 132 2.6 84.8 100 100 187.2
380/415-3-50 342 440 26.9 174 3.3 97.3 110 110 237.7
38APS UNIT
SIZE
V-Ph-Hz
SUPPLY
VOLTAGE
COMPRESSOR CONDENSER FAN
MCA MOCP
REC
FUSE
ICF
Min Max Qty RLA LRA Total Qty FLA
025
208/230-3-60 187 254
2
48.1 245
2
6.0 120.2 150 150 305.1
380-3-60 342 418 23.7 145 3.9 61.1 80 70 176.5
460-3-60 414 506 18.6 125 2.9 47.7 60 60 149.4
575-3-60 518 632 14.7 100 2.4 37.9 50 45 119.5
380/415-3-50 342 440 18.6 118 2.9 47.7 60 60 142.4
027
208/230-3-60 187 254
2
51.3 300
2
6.0 127.4 175 150 363.3
380-3-60 342 418 26.9 139 3.9 68.3 90 80 173.7
460-3-60 414 506 23.1 150 2.9 57.8 80 70 178.9
575-3-60 518 632 19.9 109 2.4 49.6 60 60 133.7
380/415-3-50 342 440 23.1 140 2.9 57.8 80 70 168.9
030
208/230-3-60 187 254
2
55.8 340
2
6.0 137.6 175 175 407.8
380-3-60 342 418 34.0 196 3.9 84.3 110 100 237.8
460-3-60 414 506 26.9 179 2.9 66.3 90 80 211.7
575-3-60 518 632 23.7 132 2.4 58.1 80 70 160.5
380/415-3-50 342 440 26.9 174 2.9 66.3 90 80 206.7
040
208/230-3-60 187 254
3
51.3 300
3
6.0 184.7 225 200 420.6
380-3-60 342 418 26.9 139 3.9 99.1 125 110 204.5
460-3-60 414 506 23.1 150 2.9 83.8 100 100 204.9
575-3-60 518 632 19.9 109 2.4 71.9 90 80 156.0
380/415-3-50 342 440 23.1 140 2.9 83.8 100 100 194.9
050
208/230-3-60 187 254
3
55.8 340
3
6.0 199.4 250 225 469.6
380-3-60 342 418 34.0 196 3.9 122.2 150 150 275.7
460-3-60 414 506 26.9 179 2.9 96.1 110 110 241.5
575-3-60 518 632 23.7 132 2.4 84.2 100 100 186.6
380/415-3-50 342 440 26.9 174 2.9 96.1 110 110 236.5
FLA Full Load Amps
ICF Maximum Instantaneous Current Flow
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps