Carrier 38APD025-100 Air Conditioner User Manual


 
10
UNIT
STANDARD
WEIGHT, lb (kg)
CENTER OF GRAVITY,
in. (mm)
HEIGHT,
in. (mm)
SERVICE VALVE
CONNECTIONS, in. (mm)
X Y H Suction Liquid
Standard
38APS040 1968 (893) 35.0 (869) 44.0 (1118)
73.0 (1854)
2
1
/
8
(54)
7
/
8
(22)
38APD040 2094 (950) 33.7 (856) 44.1 (1120) 1
5
/
8
(41)
5
/
8
(16)
38APS050 1977 (897) 34.9 (886) 44.0 (1118) 2
1
/
8
(54)
7
/
8
(22)
38APD050 2120 (961) 33.4 (848) 44.1 (1120) 1
5
/
8
(41)
5
/
8
(16)
38APD060 2227 (1010) 34.4 (874) 44.1 (1120) 1
5
/
8
(41)
5
/
8
(16)
Low Sound
38APS040 2022 (917) 35.0 (869) 44.0 (1118)
78.5 (1994)
2
1
/
8
(54)
7
/
8
(22)
38APD040 2148 (974) 33.7 (856) 44.1 (1120) 1
5
/
8
(41)
5
/
8
(16)
38APS050 2031 (921) 34.9 (886) 44.0 (1118) 2
1
/
8
(54)
7
/
8
(22)
38APD050 2174 (986) 33.4 (848) 44.1 (1120) 1
5
/
8
(41)
5
/
8
(16)
38APD060 2299 (1043) 34.4 (874) 44.1 (1120) 1
5
/
8
(41)
5
/
8
(16)
NOTES:
1. Be sure to use a wet rag to remove all valve cores before brazing field piping.
2. Do not cap or otherwise obstruct the liquid line temperature relief.
3. A
7
/
8
in. (22.4 mm) diameter hole is provided for locating field power wiring.
Actual hole size required depends on field wire sizing.
4. A 0.437 in. (11.1 mm) diameter hole is used for mounting unit.
5. Unit must have clearances as follows:
Top - Do not restrict.
Coil End - 72 in. (1829) from solid surface.
Panel Side - 48 in. (1219) per NEC (National Electrical Code, U.S.A. Standard).
6. Unit height dimension for standard and low sound unit with stack fan option.
7. Installation in a pit is not recommended.
8. Unit can be handled using the fork truck lift pockets.
9. Dimensions shown in inches (mm).
10. Sizes 040 and 050 units have 3 condenser fans. Size 060 units have 4 con-
denser fans.
a38-7102
Fig. 6 — 38AP Unit Dimensions, Sizes 040-060