Carrier 38APD025-100 Air Conditioner User Manual


 
12
UNIT
STANDARD
WEIGHT, lb (kg)
CENTER OF GRAVITY,
in. (mm)
HEIGHT,
in. (mm)
SERVICE VALVE CONNECTIONS,
in. (mm)
Suction
Liquid
X Y H Circuit A Circuit B
Standard
38APD080 2610 (1184) 67.6 (1716) 40.2 (1020)
73.0 (1854)
2
1
/
8
(54) 1
5
/
8
(41)
7
/
8
(22)
38APD090 2835 (1286) 72.4 (1839) 43.3 (1099) 2
1
/
8
(54)
7
/
8
(22)
38APD100 2844 (1290) 72.6 (1844) 43.3 (1099) 2
1
/
8
(54)
7
/
8
(22)
Low Sound
38APD080 2700 (1225) 67.6 (1716) 40.2 (1020)
78.5 (1994)
2
1
/
8
(54) 1
5
/
8
(41)
7
/
8
(22)
38APD090 2943 (1335) 72.4 (1839) 43.3 (1099) 2
1
/
8
(54)
7
/
8
(22)
38APD100 2952 (1339) 72.6 (1844) 43.3 (1099) 2
1
/
8
(54)
7
/
8
(22)
NOTES:
1. Be sure to use a wet rag to remove all valve cores before brazing field piping.
2. Do not cap or otherwise obstruct the liquid line temperature relief.
3. A
7
/
8
in. (22.4 mm) diameter hole is provided for locating field power wiring.
Actual hole size required depends on field wire sizing.
4. A 0.437 in. (11.1 mm) diameter hole is used for mounting unit.
5. Unit must have clearances as follows:
Top - Do not restrict.
Coil, Panel and Rear Side - 72 in. (1829) from solid surface.
6. Unit height dimension for standard and low sound unit with stack fan option.
7. Installation in a pit is not recommended.
8. Unit can be handled using crane.
9. Dimensions shown in inches (mm).
10. Size 080 units have 5 condenser fans. Sizes 090 and 100 units have 6 con-
denser fans.
a38-7104
Fig. 8 — 38AP Unit Dimensions, Sizes 080-100