Carrier 38AKS013-024 Air Conditioner User Manual


 
Table 6A Electrical Data (3 Ph/60 Hz)
UNIT
38AKS
UNIT COMPR FAN MOTORS (Single Phase)
Model
Volts
MCA ICF
MOCP
(Fuse
Only)
RLA LRA
Total
Fans
FLA (ea)
Fan No.
kW
Nameplate
Supplied*
Min Max 1 2
013
501 208-230 187 253 62.5 178 100 43.6 170
2
4.3 3.7
1.41
201 380 342 418 35.0 101 50 24.0 93 4.3 3.7
601 460 414 528 29.1 81 40 20.0 77 2.3 1.9
101 575 518 660 22.8 67 35 15.7 62 1.8 1.8
014
501 208-230 187 253 69.3 199 100 49.3 191
2
4.3 3.7
1.41
201 380 342 418 38.0 112 60 26.5 104 4.3 3.7
601 460 414 528 31.7 84 50 22.1 80 2.3 1.9
101 575 518 660 25.6 73 40 17.9 69 1.8 1.8
016
501 208-230 187 253 87.5 274 125 63.6 266
2
4.3 3.7
1.41
201 380 342 418 49.3 153 80 36.0 145 4.3 3.7
601 460 414 528 40.7 124 60 29.3 120 2.3 1.9
101 575 518 660 33.0 100 50 23.8 96 1.8 1.8
024
501 208-230 187 254 93.4 353 150 67.9 345
2
4.3 3.7
1.41
201 380 342 418 49.7 199 80 34.6 191 4.3 3.7
601 460 414 508 48.1 177 80 34.7 173 2.3 1.9
101 575 518 632 40.1 124 60 28.8 120 1.8 1.8
LEGEND
FLA Full Load Amps (Fan Motors)
ICF Maximum Instantaneous Current Flow during start-up
(LRA of compressor plus total FLA of fan motors)
kW Total Fan Motor Input (kilowatts)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC (U.S.A.),
Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (Compressor)
*Units are suitable for use on electrical systems where voltage sup-
plied to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance
with the National Electrical Code (NEC) article 440 (U.S.A.
standard).
2. Motor RLA and LRA values are established in accordance
with Underwriters’ Laboratories (UL) Standard 1995 (U.S.A.
standard).
LEGEND
EQUIP GND Equipment Ground
NEC National Electrical Code
Factory Wiring
Field Wiring
Fig. 7 Main Power Supply Wiring
LEGEND
C—Compressor Contactor
HD Heating Device
IFC Indoor-Fan Contactor
LLSV1 Liquid Line Solenoid Valve 1 Refrigerant Migration
Control
LLSV2 Liquid Line Solenoid Valve 2 Capacity Control
R—Relay
Factory Wiring
Field Wiring
NOTES:
1. Combination LLSV plus IFC va should not exceed 30 va.
2. Do not exceed 5 va (24 vac) per coil.
3. If va values shown in Notes 1 and 2 must be exceeded, use
accessory relay transformer package 38AE900001 (60 Hz) or
38AD900003 (50 Hz and 380-3-60).
Fig. 8 Remote Thermostat Wiring
11