Carrier 30RY/RYH Air Conditioner User Manual


 
32
The following table summarises the possible selections
depending on the control types (local, remote or CCN) and the
following parameters:
- Setpoint select in local control: item #12 of the Infor-
mation menu permits selection of the active setpoint, if
the unit is in local operating type.
- Heating/cooling operating mode
- Control contacts: status of control contacts 5 and 6 (dual-
circuit units only). These contacts are only active if the
unit is in remote control operating type. See section 3.6.6.
- Control contact 3: status of control contact 3 (single-
circuit units only). See section 3.6.4.
- Contol contact 3 selection: this selection, only used for
single-circuit units, indicates if contact 3 is used for dual
setpoint control or for demand limit control (see User
Configuration menu).
- Schedule 2 status: schedule for setpoint selection. See
section 4.3.11.6.
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
Heating
LOCAL
SETPOINT
SELECTION
sp 1
sp 2
Auto
Auto
sp 1
sp 2
sp 3
Auto
Auto
Auto
SCHEDULE 2
STATUS
-
-
Occupied
Unoccupied
-
-
-
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
LOCAL OPERATING MODE
PARAMETER STATUS
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
CONTROL CONTACT 3
SELECTION
Setpoint
Setpoint
Demand limit
Demand limit
Setpoint
Setpoint
Demand limit
Demand limit
Demand limit
CONTROL CONTACT 3
Setpoint 1
Setpoint 2
-
-
Setpoint 1
Setpoint 2
-
-
-
SCHEDULE 2 STATUS
-
-
Occupied
Unoccupied
-
-
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
REMOTE OPERATING MODE - SINGLE-CIRCUIT UNITS
PARAMETER STATUS
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Heating
Heating
Heating
SCHEDULE 2
STATUS
Occupied
Unoccupied
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
CCN OPERATING MODE
PARAMETER STATUS
HEATING/COOLING
OPERATING MODE
Cooling
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Heating
Heating
Heating
CONTROL
CONTACTS
sp 1
sp 2
sp 3
Auto
Auto
sp 1
sp 2
sp 3
Auto
Auto
Auto
SCHEDULE 2
STATUS
-
-
-
Occupied
Unoccupied
-
-
-
Occupied
Unoccupied
Holiday
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
Heating setpoint 1
Heating setpoint 2
Heating setpoint 3
REMOTE OPERATING MODE - DUAL-CIRCUIT UNITS
PARAMETER STATUS