ELECTRICAL DATA
566D150-240
LEGEND *Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
566E150-240
LEGEND *Units are suitable for use on electrical systems where voltage supplied to the
unit terminals is not below or above the listed limits.
†Fuse or HACR circuit breaker.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the National
Electrical Code (NEC), Article 440.
2. Motor RLA and LRA values are established in accordance with Underwrit-
ers’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-
installed accessory and is 115-v, 1ph, 60 Hz.
UNIT
SIZE
NOMINAL
VOLTAGE
(3-Ph, 60 Hz)
VOLTAGE
RANGE*
COMPRESSOR FAN MOTORS (Qty 2) POWER SUPPLY
RLA LRA
FLA (ea)
Fan No.
kW MCA MOCP† ICF
Min Max 1 2
566D
150
208/230 187 253 49.3 191 4.3 3.7
1.41
69.6 100 199
460 414 528 22.1 80 2.3 1.9 31.7 50 84
575 518 660 17.9 69 1.8 1.8 25.6 40 73
180
208/230 187 253 63.6 266 4.3 3.7
1.41
87.5 125 274
460 414 528 29.3 120 2.3 1.9 40.7 60 124
575 518 660 23.8 96 1.8 1.8 33.0 50 100
240
208/230 187 254 67.9 345 4.3 3.7
1.41
93.4 150 353
460 414 508 34.7 173 2.3 1.9 48.1 80 177
575 518 632 28.8 120 1.8 1.8 40.1 60 124
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
ICF Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW—Total Fan Motor Input (kilowatts)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC,
Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)
UNIT
SIZE
FACTORY-
INSTALLED
OPTION
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE*
COMPRESSOR 1 COMPRESSOR 2
FAN MOTORS
Qty 2)
POWER
SUPPLY
FLA (ea)
Fan No.
kW
Min Max RLA LRA RLA LRA 1 2 MCA MOCP† ICF
566E
150
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230 187 253 20.7 156 20.7 156 4.3 3.7 1.41
55.6 70 186
63.5 80 194
NONE OR DISCONNECT
CONVENIENCE OUTLET
460 414 528 10.0 75 10.0 75 2.3 1.9 1.41
27.7 35 90
31.3 40 94
NONE OR DISCONNECT
CONVENIENCE OUTLET
575 518 660 8.2 54 8.2 54 1.8 1.8 1.41
23.1 30 67
25.9 30 70
180
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230 187 253 32.1 195 32.1 195 4.3 3.7 1.41
81.2 100 236
89.2 100 244
NONE OR DISCONNECT
CONVENIENCE OUTLET
460 414 528 16.4 95 16.4 95 2.3 1.9 1.41
42.1 50 117
45.7 60 120
NONE OR DISCONNECT
CONVENIENCE OUTLET
575 518 660 12.0 80 12.0 80 1.8 1.8 1.41
31.6 40 97
34.5 40 99
240
NONE OR DISCONNECT
CONVENIENCE OUTLET
208/230 187 253 37.8 239 37.8 239 4.3 3.7 1.41
94.1 125 286
102.0 150 294
NONE OR DISCONNECT
CONVENIENCE OUTLET
460 414 528 19.2 125 19.2 125 2.3 1.9 1.41
48.4 60 149
52.0 70 153
NONE OR DISCONNECT
CONVENIENCE OUTLET
575 518 660 13.8 80 13.8 80 1.8 1.8 1.41
35.7 45 98
38.5 50 101
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
ICF Maximum Instantaneous Current Flow
During Start-Up (LRA of compressor
plus total FLA of fan motors)
kW—Total Fan Motor Input (kilowatts)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps per NEC,
Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)
50TFQ004-012
566D/E150-240