PERFORMANCE DATA (cont)
COMBINATION RATINGS (cont)
UNIT 566E180 (cont)
LEGEND
566E180/524A-C180 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 180.0 190.0 206.0 223.0 197.0 201.0 216.0 233.0 209.0 210.0 222.0 239.0
SHC 180.0 162.0 136.0 110.0 197.0 188.0 156.0 122.0 209.0 208.0 174.0 134.0
kW 12.90 13.20 13.60 14.00 13.30 13.40 13.80 14.20 13.60 13.70 14.00 14.40
85
TC 177.0 187.0 203.0 220.0 194.0 198.0 212.0 229.0 206.0 206.0 219.0 235.0
SHC 177.0 160.0 135.0 109.0 194.0 186.0 154.0 121.0 206.0 206.0 173.0 132.0
kW 13.50 13.80 14.20 14.60 13.90 14.00 14.40 14.80 14.20 14.20 14.60 15.00
95
TC 172.0 180.0 195.0 212.0 188.0 190.0 204.0 221.0 199.0 199.0 210.0 226.0
SHC 172.0 157.0 132.0 106.0 188.0 182.0 151.0 118.0 199.0 199.0 169.0 129.0
kW 14.70 14.90 15.40 15.80 15.20 15.20 15.60 16.10 15.50 15.50 15.80 16.20
100
TC 169.0 176.0 191.0 207.0 184.0 186.0 200.0 216.0 195.0 195.0 205.0 221.0
SHC 169.0 155.0 130.0 104.0 184.0 180.0 149.0 116.0 195.0 195.0 168.0 128.0
kW 15.40 15.60 16.00 16.40 15.80 15.80 16.20 16.70 16.10 16.10 16.40 16.90
105
TC 166.0 172.0 187.0 203.0 181.0 182.0 195.0 211.0 191.0 191.0 201.0 216.0
SHC 166.0 153.0 128.0 102.0 181.0 178.0 147.0 115.0 191.0 191.0 166.0 126.0
kW 16.00 16.20 16.60 17.10 16.40 16.50 16.90 17.40 16.70 16.80 17.00 17.50
115
TC 159.0 164.0 178.0 193.0 173.0 174.0 185.0 201.0 183.0 183.0 191.0 205.0
SHC 159.0 149.0 124.0 98.8 173.0 172.0 144.0 111.0 183.0 183.0 162.0 122.0
kW 17.30 17.50 17.90 18.40 17.80 17.80 18.10 18.60 18.10 18.10 18.30 18.80
566E180/524A-B180 WITH STANDARD 3-ROW COIL
Temp (F)
Air Entering
Condenser
(Edb)
Evaporator Air — Cfm
4500 6000 7500
Evaporator Air — Ewb (F)
57 62 67 72 57 62 67 72 57 62 67 72
80
TC 169.0 180.0 195.0 211.0 185.0 190.0 204.0 221.0 196.0 197.0 211.0 227.0
SHC 169.0 152.0 128.0 104.0 185.0 175.0 146.0 115.0 196.0 193.0 162.0 125.0
kW 12.70 12.90 13.30 13.70 13.10 13.20 13.50 13.90 13.30 13.30 13.70 14.10
85
TC 167.0 177.0 192.0 208.0 182.0 186.0 201.0 217.0 193.0 194.0 207.0 223.0
SHC 167.0 151.0 127.0 103.0 182.0 173.0 144.0 113.0 193.0 191.0 160.0 123.0
kW 13.30 13.50 13.90 14.30 13.60 13.70 14.10 14.50 13.90 13.90 14.30 14.70
95
TC 161.0 170.0 184.0 200.0 176.0 179.0 193.0 209.0 186.0 187.0 199.0 215.0
SHC 161.0 147.0 124.0 99.8 176.0 169.0 141.0 111.0 186.0 186.0 157.0 120.0
kW 14.50 14.70 15.10 15.50 14.80 14.90 15.30 15.70 15.10 15.10 15.50 15.90
100
TC 159.0 166.0 181.0 196.0 173.0 176.0 189.0 204.0 183.0 183.0 194.0 210.0
SHC 159.0 145.0 122.0 98.2 173.0 167.0 139.0 109.0 183.0 183.0 155.0 119.0
kW 15.10 15.30 15.70 16.10 15.50 15.50 15.90 16.40 15.70 15.70 16.10 16.50
105
TC 156.0 163.0 177.0 192.0 169.0 172.0 185.0 200.0 179.0 179.0 190.0 205.0
SHC 156.0 144.0 120.0 96.6 169.0 165.0 138.0 107.0 179.0 179.0 153.0 117.0
kW 15.70 15.90 16.30 16.80 16.10 16.20 16.50 17.00 16.40 16.40 16.70 17.20
115
TC 150.0 155.0 168.0 183.0 163.0 164.0 175.0 190.0 172.0 172.0 180.0 195.0
SHC 150.0 140.0 117.0 93.2 163.0 160.0 134.0 104.0 172.0 172.0 150.0 114.0
kW 17.10 17.20 17.60 18.10 17.50 17.50 17.80 18.30 17.70 17.70 18.00 18.50
Edb Entering Dry Bulb
Ewb Entering Wet Bulb
kW—Compressor Motor Power Input
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
50TFQ004-012
566D/E150-240