Bryant 566E Air Conditioner User Manual


 
70
PERFORMANCE DATA (cont)
FACTORY-SUPPLIED FILTER PRESSURE DROP ACCESSORY PLENUM AIR THROW DATA
Throw distances shown are for 75 fpm terminal velocity. Use the follow-
ing multipliers to determine throw values for other terminal velocities.
ACCESSORY PRESSURE DROP (in. wg)
UNIT
524A-B
524A-C
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
072
1,800
2,400
3,000
0.05
0.08
0.11
090
2,250
3,000
3,750
0.07
0.11
0.15
120
3,000
4,000
5,000
0.11
0.17
0.23
150
3,750
5,000
6,250
0.06
0.10
0.13
180
4,500
6,000
7,500
0.08
0.12
0.17
240
6,000
8,000
10,000
0.12
0.19
0.26
300
7,500
10,000
12,500
0.15
0.22
0.30
UNIT
524A
AIRFLOW
(Cfm)
VANE DEFLECTION
Straight 21½° 45°
072 2,400 39 33 24
090 3,000 45 38 28
102 3,400 49 41 30
120 4,000 55 46 33
150 5,000 45 38 28
180 6,000 50 43 31
240 8,000 60 51 37
300 10,000 76 65 47
TERMINAL VELOCITY
(Fpm)
THROW FACTOR
50 X1.50
100 X0.75
150 X0.50
UNIT
524A
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
HEATING COILS
ECONOMIZER
Hot Water Steam Electric
072
1,800
2,400
3,000
0.06
0.10
0.14
0.01
0.01
0.02
0.10
0.16
0.23
0.10
0.16
0.23
0.04
0.06
0.10
0.05
0.07
0.09
090
2,250
3,000
3,750
0.09
0.14
0.21
0.01
0.02
0.03
0.15
0.23
0.35
0.15
0.23
0.35
0.06
0.10
0.15
0.06
0.09
0.15
102
2,550
3,400
4,250
0.11
0.17
0.24
0.02
0.03
0.04
0.18
0.28
0.41
0.18
0.28
0.41
0.07
0.12
0.19
0.07
0.13
0.19
120
3,000
4,000
5,000
0.14
0.22
0.32
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
150
3,750
5,000
6,250
0.07
0.12
0.17
0.01
0.02
0.02
0.11
0.17
0.25
0.11
0.17
0.25
0.04
0.07
0.11
0.05
0.07
0.11
180
4,500
6,000
7,500
0.10
0.16
0.23
0.01
0.02
0.03
0.15
0.23
0.33
0.15
0.23
0.33
0.06
0.10
0.15
0.06
0.09
0.15
240
6,000
8,000
10,000
0.16
0.26
0.37
0.02
0.04
0.06
0.23
0.37
0.53
0.23
0.37
0.53
0.10
0.17
0.26
0.09
0.17
0.28
300
7,500
10,000
12,500
0.15
0.24
0.34
0.02
0.03
0.05
0.28
0.44
0.63
0.28
0.44
0.63
0.09
0.16
0.24
0.06
0.09
0.14
50TFQ004-012
524A072-300