ELECTRICAL DATA
569D072-120, 576C120, 569F120 UNITS
LEGEND *Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the
NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option
or a field-installed accessory and is 115-v, 1 ph, 60 Hz.
UNIT
SIZE
FACTORY-
INSTALLED
OPTION
NOMINAL
VOLTAGE
VOLTAGE
RANGE*
COMPRESSOR
FAN MOTORS
(Qty 2)
POWER
SUPPLY
V-Ph-Hz MIN MAX RLA LRA FLA (ea) LRA (ea) MCA MOCP
569D
072
NONE OR DISCONNECT
208/230-3-60 187 254 19.2 146 0.9 1.6
25.8 35
CONVENIENCE OUTLET 30.6 35
NONE OR DISCONNECT
460-3-60 418 506 9.6 73 0.4 0.9
12.8 20
CONVENIENCE OUTLET 15.0 20
NONE OR DISCONNECT
575-3-60 523 632 7.7 58.4 0.4 0.9
10.2 15
CONVENIENCE OUTLET 12.0 15
090
NONE OR DISCONNECT
208/230-3-60 187 254 25.6 190 1.5 3.1
35.0 60
CONVENIENCE OUTLET 39.8 60
NONE OR DISCONNECT
460-3-60 418 506 12.8 95 0.7 1.9
17.4 30
CONVENIENCE OUTLET 19.6 30
NONE OR DISCONNECT
575-3-60 523 632 10.2 76 0.7 1.9
13.8 20
CONVENIENCE OUTLET 15.5 20
120
NONE OR DISCONNECT
208/230-3-60 187 254 37.8 239 1.5 3.1
50.3 60
CONVENIENCE OUTLET 55.1 70
NONE OR DISCONNECT
460-3-60 418 506 17.2 125 0.7 1.9
22.9 30
CONVENIENCE OUTLET 25.1 30
NONE OR DISCONNECT
575-3-60 523 632 13.4 80 0.7 1.9
17.8 25
CONVENIENCE OUTLET 19.5 25
576C 120
NONE OR DISCONNECT
208/230-3-60 187 254 36 198 1.5 3.1
48.0 60
CONVENIENCE OUTLET 52.8 70
NONE OR DISCONNECT
460-3-60 418 506 18 99 0.7 1.9
23.9 35
CONVENIENCE OUTLET 26.1 35
NONE OR DISCONNECT
575-3-60 523 632 14 79 0.7 1.9
18.6 30
CONVENIENCE OUTLET 20.3 30
569F 120
NONE OR DISCONNECT
208/230-3-60 187 254 16 125 1.5 3.1
39.0 50
CONVENIENCE OUTLET 43.8 50
NONE OR DISCONNECT
460-3-60 418 506 8 66.5 0.7 1.9
19.4 25
CONVENIENCE OUTLET 21.6 25
NONE OR DISCONNECT
575-3-60 523 632 6.4 50 0.7 1.9
15.8 20
CONVENIENCE OUTLET 17.5 20
FLA Full Load Amps
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
NEC National Electrical Code
RLA Rated Load Amps