PERFORMANCE DATA (cont)
ELECTRIC HEATING CAPACITIES
*Two heater packages required to provide kW indicated.
009 for 551B102 units.
**On units with factory-installed outlet, use CRSINGLE014A00.
NOTES:
1. The kW ratings shown above are at 240, 480, and 600 v. Use the Multiplica-
tion Factors table below to determine heater capacity for your particular
voltage.
MULTIPLICATION FACTORS
Example: 32.0 kW (at 240 v) heater on 208 v
= 32.0 (.75 mult factor)
= 24.0 kW capacity at 208 v
2. Heaters are not available for size 036-072 575-v units.
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES
LEGEND
*Used to determine minimum disconnect per NEC.
Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v.
If power distribution voltage to unit varies form rated heater voltage, heater kW
will vary accordingly.
**Fuse or HACR circuit breaker per NEC.
††Units have 2 condenser-fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent of voltage
imbalance.
% Voltage ImbalanceExample: Supply voltage is 460-3-60.
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT:
If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
3. Non-fused disconnect switch cannot be used when rooftop unit electrical
ratings exceed 80 amps.
4. 575-v units have UL, Canada approval only. Electric heaters are not avail-
able for 036-072, 575-v units.
UNIT
551B
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY
SINGLE POINT BOX
PART NO.
CRSINGLE---A00
036
208/230
(single
phase)
4.4 101
6.5 102
8.7 103
10.5 104
13.0* 102* 004
208/230
(3 phase)
4.4 101
6.5 102
8.7 103
10.5 104
16.0 105
460
(3 phase)
6.0 106
8.8 107
11.5 108
14.0 109
048
208/230
(single
phase)
4.4 101
8.7 103
13.0* 102* 004
17.4* 103* 004
21.0* 104* 004
208/230
(3 phase)
6.5 102
8.7 103
16.0 105
21.0* 104* 002
460
(3 phase)
6.0 106
11.5 108
14.0 109
23.0* 108*
060
208/230
(single
phase)
6.5 102
8.7 103
13.0* 102* 004
17.4* 103* 004
21.0* 104* 004
208/230
(3 phase)
6.5 102
10.5 104
16.0 105
21.0* 104* 002
26.5* 105,104 002
460
(3 phase)
6.0 106
11.5 108
14.0 109
23.0* 108*
25.5* 109,108
072
208/230
(3 phase)
6.5 102
10.5 104
16.0 105
21.0* 104* 002
26.5* 105,104 002
460
(3 phase)
6.0 106
11.5 108
14.0 109
23.0* 108*
25.5* 109,108
UNIT
551B
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY
SINGLE POINT BOX
PART NO.
CRSINGLE---A00
090,
102
208/230
(3 phase)
10.5 117 006
16.0 110 006
24.8 111 007
32.0 112 007
42.4* 112,117 007
460
(3 phase)
14.0 116 006
16.5 113 006
27.8 114 006
33.0 115 006
41.7* 114,116 008
575
(3 phase)
17.0 118 006
34.0 119 006
120,
150
208/230
(3 phase)
10.5 117 012
16.0 110 012
32.0 112 012
42.4* 112,117 015
50.0* 112,110 015
460
(3 phase)
16.5 113 011
27.8 114 011
33.0 115 011**
41.7* 114,116 014
50.0* 115,113 014
575
(3 phase)
17.0 118 011
34.0 119 011
51.0* 119,118 014
HEATER kW
RATING
VOLTAGE DISTRIBUTION
V/3/60
MULTIPLICATION
FAC TO R
240
200
208
230
240
.69
.75
.92
1.00
480
440
460
480
.84
.92
1.00
600
550
575
600
.84
.92
1.00
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
UL
Underwriters Laboratories
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
=
457
7
457