PERFORMANCE DATA (cont)
GLYCOL HEATING PERFORMANCE
LEGEND
*
P is the fluid pressure in ft of head.
NOTES:
1. This accessory glycol coil is intended for use with a MINIMUM of 25% glycol
solution. It IS NOT intended for use solely with water due to freeze-up condi-
tions and the resulting water damage to the conditioned space.
2. Water
= 20 F.
GLYCOL COIL
Temperature
Entering
Condenser
Air Entering Evaporator Cfm
4400 5400 7200
Percent Glycol
25 50 25 50 25 50
Edb Ewt Cap Gpm Ldb Cap Gpm Ldb Cap Gpm Ldb Cap Gpm Ldb Cap Gpm Ldb Cap Gpm Ldb
55
200
310 33 120 293 33 116 347 37 115 327 37 111 405 43 107 381 43 104
180
255 27 108 237 27 105 285 30 104 264 30 101 332 35 98 306 35 95
160
200 21 97 181 21 93 223 24 94 202 23 90 259 27 89 233 27 85
70
200
274 29 127 257 29 124 306 32 123 287 33 119 357 38 116 333 38 113
180
218 23 116 201 23 112 244 26 112 224 26 109 284 30 107 259 30 104
160
164 17 104 146 17 100 183 19 101 162 19 98 212 22 97 187 22 94
80
200
249 26 132 233 27 129 279 30 128 260 30 125 325 34 122 302 34 119
180
194 21 121 177 20 117 217 23 117 197 23 114 252 26 113 228 27 109
160
140 15 109 123 14 106 156 16 107 136 16 103 180 18 103 156 19 100
GLYCOL COIL (cont)
Temperature
Entering
Condenser
Air Entering Evaporator Cfm
9000
Percent Glycol
25 50
Edb Ewt Cap Gpm Ldb Cap Gpm Ldb
55
200
453 48 102 425 48 99
180
371 39 93 342 39 90
160
290 31 85 260 30 82
70
200
400 42 111 372 42 108
180
317 34 103 287 33 100
160
237 25 94 208 24 91
80
200
364 39 118 337 38 115
180
281 30 109 254 29 106
160
201 21 101 173 20 78
GLYCOL COIL RATINGS
Entering
Fluid
Temp (F)
Cfm
4,000 5,000 6,000 8,000 10,000
Gpm
P* Gpm
P* Gpm
P* Gpm
P* Gpm
P*
200
27 1.2 31 1.5 35 1.8 41 2.4 47 2.9
180
22 0.9 25 1.1 27 1.3 32 1.6 36 2.0
160
16 0.6 19 0.7 20 0.8 24 1.0 27 1.2
Cap
Btuh × 1000
Edb
Entering Dry Bulb Temperature (F)
Ewt
Entering Water Temperature (F)
Gpm
Gallons Per Minute
Ldb
Leaving Dry-Bulb Temperature (F)