Bryant 551B Air Conditioner User Manual


 
80
PERFORMANCE DATA (cont)
COOLING CAPACITIES, STANDARD UNITS (cont)
Do not operate at these conditions.
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
where h
ewb
= enthalpy of air entering indoor coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC
.
Correction Factor = 1.10 x (1 BF) x (db 80)
551B080 (6 TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
1800/0.05 2100/0.06 2400/0.06 3000/0.08
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
93.5 86.7 80.7 74.4 95.3 88.8 82.7 76.6 97.3 90.5 84.4 78.2 92.6 86.3 81.0
SHC
29.9 43.0 53.7 63.8 30.1 45.0 57.4 68.9 30.7 47.2 61.2 73.6 51.2 67.4 80.7
kW
4.73 4.58 4.46 4.33 4.77 4.63 4.50 4.38 4.82 4.67 4.55 4.41
4.72 4.58 4.47
85
TC
91.3 84.1 78.2 72.0 93.0 86.4 80.3 74.1 88.2 81.7 75.7 90.2 84.0 78.8
SHC
29.2 42.0 52.6 62.7 29.6 44.5 56.6 68.0 46.8 60.2 72.5 50.6 67.4 78.7
kW
5.29 5.10 4.97 4.85 5.34 5.16 5.03 4.90 5.21 5.06 4.93 5.26 5.12 4.99
95
TC
89.0 81.3 75.3 69.2 83.4 77.3 71.3 85.1 78.9 72.9 87.2 80.6 76.2
SHC
28.4 41.0 51.4 61.4 43.4 55.3 66.6 45.8 59.2 71.2 50.2 65.8 76.2
kW
5.85 5.65 5.52 5.39 5.71 5.57 5.44 5.77 5.62 5.48 5.83 5.66 5.55
105
TC
77.9 72.0 66.1 80.0 73.8 68.0 81.6 75.3 69.6 83.4 77.1 73.2
SHC
39.7 50.2 60.0 42.2 54.0 65.2 44.6 57.8 69.3 49.0 64.5 73.2
kW
6.22 6.08 5.94 6.29 6.13 6.00 6.34 6.17 6.04 6.40 6.22 6.12
115
TC
74.7 68.4 61.8 75.9 70.0 64.1 77.6 71.3 66.5 78.7 73.0 70.1
SHC
38.7 48.8 58.1 40.8 52.6 63.2 43.3 56.4 66.4 46.9 63.2 70.0
kW
6.84 6.68 6.49 6.87 6.71 6.56 6.93 6.75 6.63 6.96 6.80 6.72
125
TC
70.3 63.6 57.2 71.8 65.5 59.1 72.9 66.8 61.9 74.0 68.6 66.4
SHC
37.2 47.0 55.8 39.5 51.0 59.1 41.7 55.0 61.9 45.4 61.8 66.3
kW
7.43 7.25 7.03 7.48 7.30 7.13 7.51 7.35 7.22 7.54 7.41 7.33
551B090 (7
1
/
2
TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
2250/0.095 3000/0.110 3750/0.135
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62
75
TC
111.9 105.5 96.9 87.6 113.3 107.3 99.6 90.7 114.7 110.3 101.9 93.8
SHC
35.4 50.6 63.6 75.7 35.9 53.3 69.2 83.7 38.8 58.0 76.6 92.2
kW
5.15 5.15 5.07 5.04 5.42 5.16 5.11 5.06 5.68 5.20 5.13 5.07
85
TC
108.8 102.5 93.6 83.6 111.9 105.1 96.5 87.5 114.1 107.7 99.0 90.6
SHC
34.4 49.7 62.4 73.9 35.3 52.8 68.4 82.2 35.7 57.3 75.9 90.0
kw
5.86 5.86 5.79 5.73 6.15 5.89 5.82 5.77 6.43 5.93 5.86 5.78
95
TC
107.4 98.9 90.1 79.3 109.3 101.6 92.9 83.5 110.8 103.8 95.3 87.4
SHC
34.0 48.5 61.2 71.9 34.3 51.9 67.2 80.2 34.9 56.2 74.9 87.3
kW
6.69 6.65 6.58 6.49 6.94 6.69 6.61 6.53 7.21 6.72 6.64 6.57
105
TC
103.4 95.3 86.2 75.7 97.6 88.8 79.6 100.0 91.0 84.1
SHC
32.6 47.3 59.6 70.2 50.7 65.9 78.0 55.3 73.6 84.1
kW
7.52 7.51 7.44 7.31 7.55 7.48 7.36 7.59 7.50 7.41
115
TC
91.0 82.0 71.6 93.2 84.5 75.4 95.6 86.6 80.7
SHC
45.9 58.0 68.1 49.3 64.2 75.3 54.2 72.1 80.7
kW
8.43 8.33 8.20 8.46 8.37 8.27 8.52 8.42 8.34
125
TC
86.2 77.8 68.1 88.3 80.0 71.9 90.0 81.9 77.2
SHC
44.1 56.4 66.3 47.5 62.6 71.8 52.1 70.1 77.2
kW
9.38 9.29 9.14 9.43 9.34 9.24 9.47 9.38 9.32
551B102 (8
1
/
2
TONS)
Temp (F)
Air Ent
Condenser
(Edb)
Temp (F) Air Entering Evaporator CFM/BF
2550/0.075 3000/0.09 3400/0.105 4250/0.125
Temp (F) Air Entering Evaporator Ewb
78 72 67 62 78 72 67 62 78 72 67 62 78 72 67 62
75
TC
128.1 119.5 105.7 94.8 129.8 123.1 109.1 98.7 130.3 124.8 110.7 100.2 131.3 126.3 112.8 103.4
SHC
37.4 56.5 65.7 77.8 37.8 60.2 71.7 86.3 37.9 62.2 75.8 92.8 41.0 67.8 83.3 101.2
kW
5.92 5.92 5.84 5.77 6.11 5.95 5.88 5.81 6.24 5.96 5.89 5.83 6.56 5.99 5.91 5.85
85
TC
124.9 115.5 101.9 90.6 127.1 119.7 105.4 94.8 128.1 121.4 106.9 96.1 130.1 124.0 109.1 98.7
SHC
36.5 55.1 64.3 76.1 36.8 58.9 70.5 85.1 36.8 61.3 74.5 90.5 39.7 66.2 82.9 98.5
kW
6.78 6.77 6.69 6.61 6.99 6.83 6.74 6.67 7.13 6.85 6.76 6.67 7.46 6.88 6.79 6.71
95
TC
121.5 111.3 97.7 86.6 123.5 115.0 101.2 90.6 124.3 117.2 102.6 91.7 120.1 104.8 94.5
SHC
35.5 53.7 62.8 74.2 36.0 57.4 68.9 82.9 36.1 60.0 73.0 88.6
65.0 81.5 94.5
kW
7.75 7.71 7.62 7.52 7.96 7.76 7.68 7.59 8.09 7.80 7.69 7.58 7.84 7.74 7.66
105
TC
117.0 107.2 93.5 82.5 110.5 96.7 85.9 112.1 97.9 87.6 114.9 99.9 90.5
SHC
33.5 52.2 61.3 72.7 56.0 67.4 81.2 58.4 71.4 86.6 63.5 79.5 90.5
kW
8.78 8.75 8.64 8.54 8.80 8.70 8.61 8.82 8.71 8.62 8.86 8.75 8.67
115
TC
101.9 89.2 78.0 104.7 91.8 81.5 106.7 93.1 83.3 109.2 94.9 86.3
SHC
50.2 59.5 70.7 53.7 65.7 79.5 56.6 69.5 83.1 61.5 77.8 86.3
kW
8.80 9.73 9.64 9.86 9.79 9.72 9.90 9.79 9.71 9.95 9.84 9.75
125
TC
97.3 84.3 73.1 100.0 86.8 76.0 101.3 87.9 78.7 102.9 89.5 81.9
SHC
48.7 57.7 68.5 52.4 63.9 76.0 54.8 67.9 78.7 59.1 75.7 81.9
kW
11.03 10.90 10.70 11.08 10.96 10.81 11.11 10.99 10.88 11.14 11.03 10.93
BF
Bypass Factor
Edb
Entering Dry Bulb
Ewb
Entering Wet Bulb
kW
Compressor Motor Power Input
SHC
Sensible Heat Capacity (1000 Btuh) Gross
TC
Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible heat capacity (Btuh)
1.1 x cfm
t
lwb
= wet-bulb temperature corresponding to enthalpy of
air leaving indoor coil (h
lwb
)
h
lwb
=h
ewb
total capacity (Btuh)
4.5 x cfm
0TFQ004-012
551B036-150