Bryant 551B Air Conditioner User Manual


 
147
PERFORMANCE DATA (cont)
ELECTRICAL DATA
ELECTRICAL DATA 558F180-300
See Legend and Notes on page 148.
UNIT
558F
NOMINAL
VO LTAG E
(3 Ph, 60 Hz)
VO LTAG E
RANGE
COMPRESSOR
OFM IFM
POWER
EXHAUST
ELECTRIC
HEAT*
POWER SUPPLY
NO. 1 NO. 2
Min Max RLA LRA RLA LRA Qty Hp
FLA
(ea)
Hp FLA FLA LRA kW FLA MCA MOCP
180
208/230 187 253 32.1 195 20.7 156 3 0.5 1.7 5.0 15.8/15.8
—— 82/ 82 110/110
4.6 18.8 ——86/ 86 110/110
——26/34 71/ 82 109/122 110/125
4.6 18.8 26/34 71/ 82 114/128 125/150
——42/56 117/135 166/155 175/175
4.6 18.8 42/56 117/135 172/161 175/175
——56/75 156/180 176/200 200/225
4.6 18.8 56/75 156/180 182/206 200/225
460 414 508 16.4 95 10 70 3 0.5 0.8 5.0 7.9
—— 41 50
2.3 6.0 —— 43 50
—— 32 39 59 60
2.3 6.0 32 39 62 70
—— 55 66 76 90
2.3 6.0 55 66 79 90
—— 80 96 106 125
2.3 6.0 80 96 109 125
210
208/230 187 253 30.1 225 28.8 195 3 0.5 1.7 5.0 15.8/15.8
—— 87/ 87 110/110
4.6 18.8 ——92/ 92 110/110
——26/34 71/ 82 109/122 110/125
4.6 18.8 26/34 71/ 82 114/128 125/150
——42/56 117/135 166/155 175/175
4.6 18.8 42/56 117/135 172/161 175/175
——56/75 156/180 176/200 200/225
4.6 18.8 56/75 156/180 182/206 200/225
460 414 508 15.5 114 14.7 95 3 0.5 0.8 5.0 7.9
—— 44 50
2.3 6.0 —— 47 60
—— 32 39 59 60
2.3 6.0 32 39 61 70
—— 55 66 76 90
2.3 6.0 55 66 79 90
—— 80 96 106 125
2.3 6.0 80 96 109 125
NOTE:
The CRRFCURB013A00 high static regain adapter accessory may be
used to provide horizontal supply/return.
NOTE:
The CRRFCURB013A00 horizontal supply/return adapter accessory
improves 558F180-300 fan performance by increasing external static pressure
by amount shown above. To convert from in. wg to Pa use the following formula:
in. wg x 249.1 = Pa
Horizontal Supply/Return Fan Performance with CRRFCURB013A00
High Static Regain Adapter
0TFQ004-012
558F180-300