—23—
Table 12 — Evaporator-Fan Motor Data — High-Static Motors
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range
of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this
table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 13 — Accessory/FIOP EconoMi$er IV Static Pressure* (in. wg)
LEGEND
*The static pressure must be added to external static pressure. The sum and the evaporator entering-
air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower
rpm and watts.
Table 14 — Accessory/FIOP Electric Heaters Static Pressure (in. wg)
LEGEND
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should
be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.
GENERAL FAN PERFORMANCE NOTES
1. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
fan motors up to the ratings shown will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
For additional information on motor performance refer to Evapora-
tor-Fan Motor Data, Tables 11 and 12.
2. Values include losses for filters, unit casing, and wet coils. See
Tables 13 and 14 and Fig. 36 for accessory/FIOP static pressure
information.
3. Use of a field-supplied motor may affect wire sizing. Contact
Bryant representative to verify.
4. Interpolation is permissible. Do not extrapolate.
UNIT
5551B
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
UNIT VOLTAGE
MAXIMUM
AMP DRAW
090,102 Three 4.20 3775
208/230 12.2
460 5.5
575 5.5
120 Three 5.25 4400
208/230 17.3
460 8.5
575 8.5
COMPONENT
CFM
2250 2500 2750 3000 3250 3500 3750 4000 4250 4500 4750 5000 5250 6250
Vertical EconoMi$er IV 0.06 0.075 0.09 0.115 0.13 0.15 0.17 0.195 0.22 0.25 0.285 0.325 0.36 —
Horizontal EconoMi$er IV — 0.1 0.125 0.15 0.18 0.21 0.25 0.275 0.3 0.34 0.388 — — —
FIOP — Factory-Installed Option
COMPONENT
CFM
2200 2500 3000 3500 4000 4500 5000 5500 6000
1 Heater Module 0.02 0.03 0.05 0.065 0.08 0.10 0.12 0.14 0.155
2 Heater Modules 0.03 0.05 0.07 0.09 0.12 0.14 0.16 0.19 0.21
FIOP — Factory-Installed Option