Bryant 551B Air Conditioner User Manual


 
12
3. Use a wire nut to connect humidistat cable into low-
voltage wiring as shown in Fig. 13.
To install Thermidistat™ device:
1. Route Thermidistat cable through hole provided in
unit corner post.
2. Feed the wires through the raceway built into the cor-
ner post to the 24-v barrier located on the left side of
the control box. See Fig. 10. The raceway provides the
UL-required clearance between high and low voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat device and the Perfect Humidity™ cir-
cuit (recommended relay: HN612KK324) Fig. 14. The
relay coil is connected between the DEHUM output
and C (common) of the unit. The relay controls the
Perfect Humidity solenoid valve and must be wired
between the Perfect Humidity fuse and the low-
pressure switch. Refer to the installation instructions
included with the Bryant Light Commercial Thermi-
distat device for more information.
Fig. 12 — Light Commercial Thermidistat Device
Fig. 13 — Typical Perfect Humidity Dehumidification System Humidistat Wiring (208/230-v Unit Shown)
CB Circuit Breaker
CR Cooling Relay
DHR Dehumidify Relay
DSV Discharge Solenoid Valve
HR Heater Relay
HU Humidistat
LPS Low Pressure Switch
LSV Liquid Solenoid Valve
LTLO Low Temperature Lockout
TB Terminal Block
TRAN Transformer
Field Splice
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
LEGEND
ROOF TOP UNIT
R
C
Y1
Y2
G
W1
W2
PINK
PINK
RED
24 V
FROM
PERFECT HUMIDITY
SYSTEM LLSV
R1
T STAT WIRES
LCT
R
C
Y1
Y2
G
W1
W2
DEHUM
OC
R1
PERFECT HUMIDITY SYSTEM
PINK
LTLO
CB
3.2 AMPS
Fig. 14 — Typical Rooftop Unit with Perfect Humidity Dehumidification System with Thermidistat Device
LEGEND
CB Circuit Breaker
LCT Light Commercial Thermidistat Device
LLSV Liquid Line Solenoid Valve
LTLO Low Temperature Lockout
% RELATIVE HUMIDITY
Fig. 11 — Accessory Field-Installed Humidistat