GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air-- cooled, split--system heat pump unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller-- type
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
Unit will be rated in accordance with the latest e dition
of ARI Standard 240.
Unit will be certified for capacity and efficiency, and
listed in the latest ARI directory.
Unit construction w ill comply with latest edition of
ANSI/ ASHRAE and with NEC.
Unit will be cons tructed i n accordance with UL
standards and will carry the UL label of approval. Unit
will have C-- UL approval.
Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500--hr
salt spray test.
Air-- cooled condenser coils are pressure tested and the
outdoor units are leak tested.
Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is
stored and handled per unit manufacturer’s
recommendations.
Warrant y (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTS
Equipment
Factory a ssembled, single piece, air--cooled heat pump
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
Puronr (R-- 410A), and special features required prior
to field start--up.
Unit
Cabinet
Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
Fans
Condenser fan will be direct--drive propeller type,
discharging air upward.
AIR--COOLED, SPLIT--SYSTEM HEAT PUMP
265A
1 --1/2 TO 5 NOMINAL TONS
Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel
wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration
isolators.
Condenser
Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration
Components
Refrigeration circuit components will include
liquid --line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of Puronr (R--410A) refrigerant, POE
compressor oil, accumulator, and reversing valve.
Operating Characteristics
The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F. The power
consumption at full load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F wet bulb
and _____ _F dry bulb, and air entering the unit at
_____ _F.
The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirement s
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Fe atures
Refer to section of this literature identifying accessories
and descriptions for specific f eatures and available
enhancements.