ELECTRICAL DATA
UNIT SIZE V/PH
OPER VOLTS* COMPR FAN
MCA
MIN WIRE
SIZE{
MIN
WIRE
SIZE{
MAX
LENGTH
(ft.)}
MAX
LENGTH
(ft.)}
MAX FUSE**
or CKT BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
018---A
208---230/1 253 197
48 9.0 0.75 12 14 14 66 62 20
024---A 58.3 12.8 0.75 16.8 14 14 47 45 25
030---A 77 14.1 0.75 21.4 12 12 58 56 30
036---A 79 16.7 1.4 22.2 12 12 56 54 35
042---A 109 19.9 1.2 26 10 10 77 73 40
048---A 117 21.8 1.2 35.4 8 8 88 84 50
060---A 134 26.3 1.2 34.1 8 8 91 87 50
* Permissible limits of the v oltage range at which t he unit will operate satisfactorily
{ If wire is applied at ambient greater t han 30° C(86° F), consult table 310---16 of the NE C (ANSI/NFPA 70). The ampacity of non---metallic--- sheath ed cable
(NM), trade name ROMEX, shall be that of 60° C (140° F) co nditions, per the NEC ( ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60
or 75° C (140 or 167° C) insulation, copper wi re (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
A--WEIGHTED SOUND LEVEL (DBA)
UNIT SIZE
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
018---A 75 54 63 68.5 71.5 68 63.5 57
024---A 75 54.5 64 69 69.5 67.5 64 58
030---A 74 52 62.5 66.5 68.5 65 63.5 59
036---A 76 60 64 69.5 70 68.5 65.5 60.5
042---A 77 55.5 60 63.5 71.5 65 62.5 59
048---A 78 57 64 68 74 67 63 58.5
060---A 76 58.5 63 68 70.5 66.5 64.5 59.5
A--WEIGHTED SOUND LEVEL (DBA) WITH SOUND SHIELD
UNIT SIZE
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
018---A 74 53.5 63.0 68.0 70.0 67.5 63.0 56.5
024---A 74 54.0 63.5 69.0 69.0 67.5 63.5 57.5
030---A 74 51.5 62.0 66.5 67.5 64.5 62.0 57.5
036---A 76 58.5 63.5 69.5 70.5 69.0 65.5 60.5
042---A 75 55.0 60.5 63.5 69.0 64.5 61.5 56.0
048---A 75 57.5 63.0 67.5 71.5 65.5 60.5 54.5
060---A 75 58.5 62.5 67.5 69.0 64.5 61.5 56.0
CHARGING SUBCOOLING (TXV --TYPE EXPANSION DEVI CE)
UNIT SIZE---SERIES REQUIRED SUBCOOLING (_F)
018---A 10
024---A 12
030---A 11
036---A 10
042---A 11
048---A 11
060---A 12
213A