Bryant 213A Heat Pump User Manual


 
3
PHYSICAL DATA
UNIT SIZE SERIES 018---A 024---A 030---A 036---A 042---A 048---A 060---A
Operating Weight (lb) 146 162 203 207 246 263 279
Shipping Weight (lb) 169 189 235 239 278 293 311
Compressor Type Scroll
REFRIGERANT Puron® (R---410A)
Control TXV (Puron Hard Shutoff)
Charge (lb) 5.25 5.9 7.6 7.65 8.4 11.75 12.35
COND FAN Propeller Type, Direct Drive
Air Discharge Vertical
Air Qty. (CFM) 2196 2614 2614 3365 3810 4046 4046
Motor HP 1/10 1/10 1/10 1/4 1/5 1/5 1/ 5
Motor RPM 1100 1100 1100 1100 800 800 800
COND COIL
Face Area (Sq. ft.) 13.13 15.09 25.87 25.87 25.15 20.12 22.63
Fins per In. 25 20 20 20 20 20 20
Rows 1 1 1 1 1 2 2
Circuits 4 5 6 6 6 8 8
VALVECONNECT.(In.ID)
Vapor 5/8 5/8 3/ 4 3/4 7/8 7/8 7/8
Liquid 3/8
REFRIGERANT TUBES* (In. OD)
Vapor (0---80 ft. Tube Length) 5/8 5/8 3/4 3/4 7/8 7/8 1 --- 1/8
Liquid (0---80 ft. Tube Length) 3/8
* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
PURON 1--STAGE HEAT PUMP APPLICATIONS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80
ft. or when there is more than 20 ft. vertical separation between
indoor and outdoor units. These applications require additional
accessories and system modifications for reliable system
operation. The maximum allowable total equivalent length is 250
ft. The maximum vertical separation is 200 ft. when outdoor unit
is above indoor unit, and 80 ft. when the outdoor unit is below
the indoor unit. Refer to Accessory Usage Guideline below for
required accessories. See Longline Application Guideline for
required piping and system modifications. Also, refer to the table
below for the acceptable vapor tube diameters based on the total
length to minimize the cooling capacity loss.
Unit Nominal Size (Btuh)
Acceptable
Vapor Line
Diameters
(In.OD)
Cooling Capacity Loss (%)Total EquivalentLine Length (ft.)
Standard Application Long Line Application Requires Accessories
25 50 80 80+ 100 125 150 175 200 225 250
18000
1 ---Stage Puron HP
1/2 1 2 3 3 4 6 7 8 9 10 12
5/8 0 0 1 1 1 1 2 2 3 3 3
24000
1 ---Stage Puron HP
5/8 0 1 1 1 2 3 3 4 4 5 6
3/4 0 0 0 0 0 1 1 1 1 1 2
30000
1 ---Stage Puron HP
5/8 1 2 3 3 3 4 5 6 7 8 9
3/4 0 0 1 1 1 1 2 2 2 3 3
7/8 0 0 0 0 0 1 1 1 1 1 1
36000
1 ---Stage Puron HP
5/8 1 2 4 4 5 6 7 9 10 11 13
3/4 0 0 1 1 1 2 2 3 3 4 4
7/8 0 0 0 0 0 1 1 1 1 2 2
42000
1 ---Stage Puron HP
3/4 0 1 2 2 2 3 4 4 5 6 6
7/8 0 0 1 1 1 1 2 2 2 3 3
48000
1 ---Stage Puron HP
3/4 0 1 2 2 3 4 5 5 6 7 8
7/8 0 0 1 1 1 2 2 2 3 3 4
60000
1 ---Stage Puron HP
3/4 1 2 4 4 5 6 7 9 10 11 12
7/8 0 1 2 2 2 3 4 4 5 5 6
11/8 0 0 0 0 1 1 1 1 1 1 2
Standard Length = 80 ft. or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See
Long Line Application Guidelines
213A