Bradford-White Corp 07.05.228.00 Water Heater User Manual


 
INSTALLATION
Form No. EBOOSTERBWM-1009
10
Temperature/Pressure Gauge
Temperature/Pressure Relief Valve
150 psi (1034 kPa)/210°F (99°C)
3/4″ Union*
Pressure Reducing Valve w/Bypass.
Maximum 20 psi (138 kPa)
flow pressure.
Temperature/Pressure
Gauge
Outlet to
dish
machine
Shock Absorber †
Drain Valve*
3/4″ Union*
Floor Drain
Outlet
Inlet
Discharge from T/P relief valve.
Air gap must comply with plumbing code.
Blended Phosphate Water
Treatment System †
† Optional accessory * Not supplied with booster water heater
3/4″ Gate or
Ball Valve*
Water inlet
from regular
water heater
Figure 5. Plumbing Connections - Magnum Series 6-18 kW
Temperature/Pressure Gauge
Temperature/Pressure Relief Valve
150 psi (1034 kPa)/210°F (99°C)
3/4″ Union*
Pressure Reducing Valve w/Bypass.
Maximum 20 psi (138 kPa)
flow pressure.
Temperature/Pressure
Gauge
Outlet to
dish
machine
Shock Absorber †
Drain Valve*
3/4″ Union*
Floor Drain
Outlet
Inlet
Discharge from T/P relief valve.
Air gap must comply with plumbing code.
Blended Phosphate Water
Treatment System †
† Optional accessory * Not supplied with booster water heater
3/4″ Gate or
Ball Valve*
Water inlet
from regular
water heater
Figure 6. Plumbing Connections - Magnum Series 24-57 kW
Figure 7. Booster Water Heater with Optional Back Pressure Relief Valve
Temperature/Pressure Gauge
Temperature/Pressure Relief Valve
150 psi (1034 kPa)/210°F (99°C)
3/4″ Union*
Pressure Reducing Valve w/Bypass.
Maximum 20 psi (138 kPa)
flow pressure.
Temperature/Pressure
Gauge
Outlet to
dish
machine
Back Pressure
Relief Valve
Shock Absorber †
Drain Valve*
3/4″ Union*
Floor Drain
Floor Drain
Outlet
Inlet
Discharge from T/P relief valve.
Air gap must comply with plumbing code.
Discharge from back pressure
relief valve. Air gap must
comply with plumbing code.
Blended Phosphate
Water Treatment
System †
† Optional accessory * Not supplied with booster water heater
3/4″ Gate or
Ball Valve*
Water inlet
from regular
water heater