Bosch Appliances THE DCN Home Security System User Manual


 
SC & SI Remote Interface Description en | 16
Bosch Security Systems B.V. | 2003 December | SC & SI Remote Interface Description
Single-Multi System, i.e. a Multi CCU system but one or more of the Slave CCU’s configured to run in Single
Mode
Event Update Notification Continue with remote function
Remote Controller connected to CCU-A, a CCU configured to run in Single CCU mode
Switch On CCU-A SC_C_CCU_REBOOT SC_C_START_DCN
Recommended before continuing:
SC_C_GET_CCU_VERSIONINFO
SC_C_GET_CCU_CONFIG
SI_C_START_INSTALL and run
installation as described in
example-1 in Appendix Appendix C
Switch On the Master
CCU
<None>
Switch On another CCU
(Slave or Single-
Mode)
<None>
Disconnect another
CCU (Slave or Single-
Mode)
<None>
Connect a unit to
CCU-A.
SC_C_CONNECT_UNIT Recommended before continuing:
SI_C_START_INSTALL and run
installation as described in
example-2 in Appendix Appendix C
Disconnect a unit
from CCU-A.
SC_C_DISCONNECT_UNIT
Connect a unit to
another CCU (Slave or
Single-Mode).
<None>
Disconnect a unit
from another CCU
(Slave or Single-
Mode).
<None>
Remote Controller connected to the Master CCU
Switch On CCU-A <None>
Switch On the Master
CCU.
SC_C_CCU_REBOOT SC_C_START_DCN
Recommended before continuing:
SC_C_GET_CCU_VERSIONINFO
SC_C_GET_CCU_CONFIG
SI_C_START_INSTALL and run
installation as described in
example-1 in Appendix Appendix C
Switch On a Slave CCU SC_C_CONNECT_SLAVE_CCU
and a few seconds later for
every unit connected to that
Slave CCU separately
SC_C_CONNECT_UNIT
Recommended before continuing on
the unit connect updates:
SI_C_START_INSTALL and run
installation as described in
example-2 in Appendix Appendix C
Switch On another
Single-Mode CCU
<None>
Switch Off a Slave
CCU
SC_C_DISCONNECT_SLAVE_CCU
Switch Off another
Single-Mode CCU
<None>
Connect a unit to
CCU-A.
<None>
Disconnect a unit
from CCU-A.
<None>
Connect a unit to a
Slave CCU.
SC_C_CONNECT_UNIT Recommended before continuing:
SI_C_START_INSTALL and run
installation as described in
example-2 in Appendix Appendix C
Disconnect a unit
from a Slave CCU.
SC_C_DISCONNECT_UNIT
Connect a unit to
another Single-Mode
CCU.
<None>
Disconnect a unit
from another Single-
Mode CCU.
<None>