Reset Time
Default: 0
Selections: 0 to 90
Use to program the reset timer for the Class “A” Alarm
Initiating Circuit (Zone 1). Enter the number of seconds
you want for the reset time. Before the retard timer sets
to zero, the circuit must be in a non-alarm (restored or
trouble) condition for the number of seconds entered in
Reset Time.
For a detailed explanation of the reset timer, refer to
Section 2.2.2 Retard and Reset Times on pages 10 and 11.
Hrs Til Rpt
Default: 0
Selections: 0 to 25
Use to program the number of hours until the first Test
Report is sent. Program the number of hours from the
time the control panel is powered up (or reset with the
programmer) to the time the first Test Report is sent.
If both Hrs Til Rpt and Min Til Rpt are defaulted at 0,
the first Test Report is sent in 12 h and all subsequent
reports are sent at 24-hour intervals thereafter.
Mins Til Rpt
Default: 0
Selections: 0 to 59
Use to program the number of minutes until the first
Test Report is sent. Program the number of additional
minutes you want the first Test Report delayed beyond
the hours programmed in Hrs Til Rpt.
Test Timer Default Delay: When the unit is powered
up, the first test occurs 12 h later unless you program a
delay in Hrs Til Rpt or Mins Til Rpt.
4.0 Program Record