3.8 Program Modules
Unlike larger Bosch products, the D2071 Product
Handler does not group program items in program
modules. When you enter the 2071 program, you are in
the Program Item Level.
3.9 Editing the Program Record
Each D2071A DACT programming option is listed as it
appears in the Programmer Display. The default, a set of
selections, and a description follows.
The selections are the only entries available for a
particular program option. For example, Account #
only uses numbers 0 through 9, letters B through F, or
no entry. Do not use unlisted entries.
To edit program options, change the entry and press
[ENTER]. If the entry is valid, the programmer moves
the cursor to the next prompt. When all program
options in the record are edited, the programmer returns
to the first program option in the record.
You can exit from any point within the program by
pressing [EXIT GROUP] until PRODUCT HANDLERS
appears on the D5200 Programmer.
4.0 Program Record
The 2071 Program Record selects several functions of
the D2071A DACT, including the account number that:
identifies the location during communication,
decides how the telephone number is dialed,
determines how the D2071A is powered, and
controls the loop response times.
Account #
Default: Blank
Selections: 0 to 999, BBB to FFF, or Blank
Ensure all entries are right-justified. The blank entry,
equaling no account number, sends 000 in pulse that
sends nothing in the BFSK format.
Transmit BFSK
Default: Yes
Selections: Yes or No
Yes Transmit in BFSK format with
2300 Hz acknowledgement.
No Transmit in fast, single-round,
expanded pulsed format with a
checksum digit and 2300 Hz
acknowledgement.
Use to select the reporting format.
DTMF Dialing
Default: Yes
Selections: Yes or No
Yes Dual tone multi-frequency dialing of
telephone numbers.
No Pulse dialing of telephone numbers.
PriPre
Default: Blank
Selections: 0 to 9, B to F, or Blank
Blank No prefix or area code. A delay up
to 7 sec is automatically inserted in
front of the prefix.
Use to select the prefix for the primary receiver
telephone number. You can enter up to nine characters.
Refer to Table 9 on page 21 for other dialing character
selections.
4.0 Program Record