Bacharach HGM300 Carbon Monoxide Alarm User Manual


 
Setup Screen #2
10) Press “LEAK LEVEL” button. Use left/right keys to move across and up/down keys to readjust leak
alarm PPM level to desired PPM level.
11) Press “SPILL LEVEL” button. Repeat as in step 8.
12) Press “EVACUATE LEVEL” Button. Repeat as in step 8.
NOTE: The evacuate level must be greater than or equal to the spill level, which must be greater
than or equal to the leak level.
13) Press “RESET PEAK” button. Use the to clear the previous peak PPM displayed for this zone.
This key is used to clear the peak PPM for this zone, which is displayed at the top of this screen. The
peak PPM gives the PPM level, time and date of the highest refrigerant readings since the unit was
last cleared (or started, if the reading has never been cleared). The peak PPM reading along with the
TREND DATA can be a powerful diagnostic tool in detecting small leaks before they become large
leaks.
14) To move to the next zone setup screen, press the right keypad button. Use the “BACK” button to
move to the first zone set up screen. Repeat steps 2 thru 13 to program the second zone. Repeat as
necessary for all zones in monitor.
15) To return to the SYSTEM SCREEN, press “QUIT” then press “SYSTEM”.
15