Bacharach 3015-4286 Carbon Monoxide Alarm User Manual


 
16 Instruction 3015-4286
DIAGNOS – Enters the diagnostic function. Press the Up Arrow
Keypad button to toggle between the monitor’s two diagnostic screens.
Refer to
Working with the DIAGNOS Function (Page 21).
GASTYPE – Ammonia monitors do not have a library of other gases to
choose from, therefore R717 is the only gas type listed. Press QUIT to
return to the previous screen.
LEAKLVL – Sets the Leak Alarm level, adjustable from 1 to 300 ppm.
Factory default is 100 ppm. Note that the Leak Alarm level cannot be set
higher than either the Spill or Evacuate Alarm levels. Use the Keypad to
set the desired Leak Alarm level, and then press ENTER to save that
level and return to the previous screen.
SPILLLVL – Sets the Spill Alarm level, adjustable from no lower than
the Leak Alarm level to a maximum value of 500 ppm, but not higher
than the Evacuate Alarm level. Factory default is 300 ppm. Use the
Keypad to set the desired Spill Alarm level, and then press ENTER to
save that level and return to the previous screen.
EVACLVL – Sets the Evacuate Alarm level, adjustable from no lower
than the Spill Alarm level to 9999 ppm. Factory default is 500 ppm. Use
the Keypad to set the desired spill level alarm level, and then press
ENTER to save that level and return to the previous screen.
LOG INT – Sets the interval at which measurements are logged to
memory from 1 to 9999 minutes. Factory default is 10 minutes. Note that
the logged measurements can be viewed using the PPM LOG function.
Use the Keypad to enter the desired value, and then press ENTER to
save that value and return to the previous screen.
LOOP – Adjusts the loop factor of the 4–20 mA current loop. Factory
default is 0.016 mA per ppm, which provides an output range of 0 ppm
(4 mA) to 1,000 ppm (20 mA). Use the Keypad to set the desired loop
factor, and then press ENTER to save that value and return to the
previous screen.
To facilitate loop zero and span checking, note that when the LOOP
function is selected the loop output is set to 20 mA, and upon exiting this
function the loop output is set to 4 mA.
AUDALRMAllows the monitor’s internal audible alarm to be
associated with any function of the monitoring system. Factory default is
OFF. Use the Keypad to select the desired audible alarm function, and
then press ENTER to save that value and return to the previous screen.
Audible Alarm Settings: OFF, ANY ALARM, SYSTEM FAULT, LEAK ALARM,
SPILL ALARM, EVAC ALARM, MONITOR STOPPED
NOTE: MONITOR STOPPED indicates there is a critical system fault, and the
monitor is no longer functioning correctly.
L
OG INTERVAL IS
0010 min
E
DIT LOOP FACTOR
0.016 ma/P
P
M
A
UDIBLE ALARM IS
OFF
4
.265
0
0v <0000>
2
4.5cD 14.00
p
si
0.4ppm 0.00
0
.00002au 4.260v
S
ELECT GAS TYPE
R717
E
DIT EVAC LEVEL
0500 PPM
E
DIT LEAK LEVEL
0
100 PPM
E
DIT SPILL LEVEL
0300 PPM