Bacharach 3015-4286 Carbon Monoxide Alarm User Manual


 
10 Instruction 3015-4286
Connecting External Alarms
Overview
The AGMSZ includes four SPDT relays whose contacts are rated 3 A at 240 VAC. These relays are used for
the connection of external alarm devices that are activated when the relay is energized. The relays are
factory assigned to energize under the following conditions:
Relay #1 Leak Alarm Point 100 ppm
Relay #2 Spill Alarm Point 300 ppm
Relay #3 Evacuate Alarm Point 500 ppm
Relay #4 Fault System Fault Event
Note that the alarm points of relays #1, #2, and #3 are set using the monitor’s LEAKLVL, SPILLLVL,
and EVACLVL function screens (Page
16).
Connection
Use any of the service knockouts to gain cable access to the interior of the monitor. Locate the External
Alarm Relay Connector (Page
8). Secure the leads from the external alarm device and its power source to
the connector as shown in the diagram below.
The diagram on Page 11 shows a typical alarm device being connected to Relay 1. Note how power to this
device is being tapped off the monitor’s AC input.
External Alarm Relay Connector
Each relay may be connected as normally open (NO), or normally closed (NC).
The relay contacts are rated 3 A at 250 VAC.
Power for the external alarm devices may be supplied from an external power source, or from
the monitor’s AC input terminals.