14 Installation (For Qualified Installers Only)
© Travis Industries 4070806 100-01191_000
Installation Example: Direct "Through-the-wall" Installation
Floor Protection
House Shield (used to protect
exterior wall from soot
discoloration) is HIGHLY
RECOMMENDED
12” Minimum
Horizontal Rain Cap
Wall Thimble
(note 3” clearance
between vent and
combustibles)
Type "L" Vent
12”
Minimum
3” Minimum
17-1/4”
Floor Protection
Seal each vent
section (including
adapters, elbows,
etc...) by injecting a
liberal amount of
500° F. RTV
silicone into the gap
between sections.
500° F. RTV
Silicone
3” Minimum
7” Minimum
6” Minimum