14 Stove Installation (for qualified installers only)
© Travis Industries 100-01190_000 4070326
Alcove Installation Requirements
Whenever the stove is placed in a location where the ceiling height is less than 8' tall, it is considered an
alcove installation. Because of the reduced height, the special installation requirements listed below must
be met.
• Chimney connector and chimney must be one of the following types:
AMERI-TEC model DCC connector with AMERI-TEC UL 103 HT chimney
DURAVENT model DVL connector with DURAVENT UL 103 HT chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel HP connector with I.C.C. UL 103 HT chimney
METALFAB model DW connector with METALFAB UL 103 HT chimney
OLIVER MACLEOD PROVENT model PV connector with OLIVER MACLEOD UL 103 HT chimney
SECURITY model DP connector with SECURITY UL 103 HT chimney
SELKIRK model DSP connector with SELKIRK UL 103 HT chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.
• The clearances below must be met:
Minimum Clearance
(See Figure 10 below)
Combustible
Alcove
A Sidewall to stove 18.00"
B Backwall to stove 20.75"
D Connector to sidewall 28.25"
E Connector to backwall 14.00"
G Maximum depth of alcove 48.00"
H Minimum width of alcove 63.25"
J Minimum height of alcove 84.00"
a
d
e
h
j
g
b
Figure 10