Avalon Stoves Arbor Stove User Manual


 
8 Stove Installation (for qualified installers only)
© Travis Industries 100-01190_000 4070326
Floor Protection Requirements
Floor protection must extend 6" to the sides and rear of the stove and 16" to the front of the stove
39.25” wide by 44.875" deep - see Figure 2 and Figure 3).
Floor protection must be non-combustible and at least .018" thick (26 guage).
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36"
of the front of the stove
Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
Clearances
The following clearances must be met (see Figure 2 and Figure 3)
Minimum Clearance Singlewall
Connector
Singlewall
Connector with
Pipe Shield**
Reduced
Clearance*
A Sidewall to stove 18.00” 18.00” 18.00”
B Backwall to stove 27.25” 17.25” 20.75”
C Cornerwall to stove 19.00” 14.00” 14.00”
D Connector to sidewall 28.75” 28.75” 28.25”
E Connector to backwall 21.00” 11.00” 14.00”
F Connector to cornerwall 23.00” 18.00” 17.50”
*Reduced clearance installations require one of the chimneys and connectors listed below:
AMERI-TEC model DCC connector with AMERI-TEC UL 103 HT chimney
DURAVENT model DVL connector with DURAVENT UL 103 HT chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel HP connector with I.C.C. UL 103 HT chimney
METALFAB model DW connector with METALFAB UL 103 HT chimney
OLIVER MACLEOD PROVENT model PV connector with OLIVER MACLEOD UL 103 HT chimney
SECURITY model DP connector with SECURITY UL 103 HT chimney
SELKIRK model DSP connector with SELKIRK UL 103 HT chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter
may be required.
NOTE: Mobile Home installations must use the reduced clearance connector and clearances
listed above.
NOTE: Standard residential installations with reduced clearance connector may use the
“Connector to Wall” clearance determined by the connector manufacturer if approved by
local code. This clearance is established by the connector manufacturer and falls under
the connector manufacturer’s listing. “Stove to Wall” clearances must always be met.
** The pipe shield must meet NFPA 211 guidelines (such as the HomeSaver® Stovepipe shield) and
must extend from the flue collar to a location 16” below the ceiling.