Stove Installation (for qualified installers only) 13
© Travis Industries 100-01190_000 4070326
Chimney Termination Requirements
• Must have an approved cap (to prevent water from entering)
• Must not be located where it will become plugged by snow or other material
• Must terminate at least 3' above the roof and at least 2' above any portion of the roof within 10' (see
Figure 8)
Slanted Roofs
F
lat Roofs
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Chimney must
extend 3'
above the roof
Chimney must extend 2'
above any portion of the roof
within 10' of the chimney
Figure 8
Outside Air Requirements
• Required for mobile homes and in certain localities (check with building officials)
• Must not be drawn from an enclosed space (garage, unventilated crawl space)
• Requires 3” aluminum duct (do not use plastic “dryer-vent”) and a hose-clamp for securing to the
stove. Maximum 4’ length. NOTE: A 10’ length is allowed if using 4” diameter duct (use a 3” to 4”
converter).
• If using the optional blower, you may need to “ovalize” the duct to route it under the blower box.
3” Air Duct (max. 4’ length)
A screen is required to prevent
rodents from entering.
Outside air entrance must be placed so it
does not become blocked by snow.
Air may be drawn from a ventilated crawl space.
Botttom of Stove
Use a hose clamp to secure the
aluminum air duct to the air inlet
flange on the stove.
Air Duct (3” Dia.)
Figure 9