Ariston E-COMBI 24 30 38 Boiler User Manual


 
19
installation
Fitting the Coaxial Flue
(Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
2x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
2x Flue Clamps
4x Screws
2x Seals
Once the boiler has been positioned on the wall,  t the rubber  ue
seal into the internal  ue turret (see diagram opposite),
insert the elbow into the socket and rotate to the required position.
Note: It is possible to rotate the elbow 360° on its vertical axis.
Using the  ue clamp, seals and screws supplied (Fig 4) secure the
elbow to the boiler.
The 1 metre horizontal  ue kit (3318073) supplied is suitable for an
exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face
of the  ue elbow (X - Fig 2), this  gure must now be subtracted from
753mm, you now have the total amount to be cut from the plain end
of the  ue.
Draw a circle around the outer  ue and cut the  ue to the required
length taking care not to cut the inner  ue, next cut the inner
ue ensuring that the length between the inner and outer  ue is
maintained. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the  ue).
Once cut to the required length, ensure that the  ue is free from burrs
and reassemble the  ue. If  tting the  ue from inside of the building
attach the grey outer wall seal to the  ue terminal and push the  ue
through the hole, once the wall seal has passed through the hole, pull
the  ue back until the seal is  ush with the wall. Alternatively, the
ue can be installed from outside of the building, the grey outer seal
being  tted last.
Should the  ue require extending, the  ue connections are push  t,
however, one  ue bracket should be used to secure each metre of  ue.
Note: See table for maximum and minimum  ue runs.
In the event that extension pieces need to be shortened, they must
only be cut at the male end and it must be ensured that the inner and
outer  ue remain  ush.
150 mm
118
Installation without extension
Installation with extension
Level
* pente 5 mm par mètre
150 mm
* pente
Level
slope
Fig. 3
Fig. 4
Slope min 1° per metre
max 3° per metre (1° = 17mm)
Clamp
Seal
Screws