To calculate the size of the heating installation, refer to the
"Available pressure" graph below.
Graph representing the available circulation pump pressure
T20
o
C
Before the equipment is used, for the rst time the trap
must be lled with water. To do this, add approximately
1/4 litre of water via the ue outlet before tting the ue
system, or unscrew the cap on the trap positioned under-
neath the boiler, ll it with water and re t it
Warning! Insu cient water in the trap can temporarily
cause the ue gas to be expelled into the surrounding
ambient air
Under oor heating
For appliances with under oor heating, it is possible but not
necessary to t a safety thermostat onto the under oor heating
outlet. For the electrical connection of the thermostat see the
section on “Electrical connections - page 25”.
If the outlet temperature is too high, the boiler will stop both
domestic hot water and the heating production and the error
code 1 16 “ oor thermostat contact open” will appear on the
display. The boiler will restart when the thermostat is closed
during automatic resetting.
If the thermostat cannot be installed, the under oor heating
equipment must be protected by a thermostatic valve, or by a by-
pass to prevent the oor from reaching too high a temperature.