Ariston 41-116-07 Boiler User Manual


 
21
The boiler can be converted to use either methane (natural) gas (G20)
or LPG (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
1. Replace the jets on the main burner (see table in section 5);
2. Adjust the maximum and minimum thermal capacity values for the boiler
(see table in section 5);
3. Replace the gas rating plate;
4. Adjust the maximum thermal power setting;
5. Adjust the soft-light feature (open the cover of the regulation screw on the
gas valve (see F
IG. 5.1). Rotate clockwise from min. to max. as per
installation requirements).
5.1 C
HANGING THE
T
YPE OF GAS
The outlet pressure of the gas cock is obtained by completely loosening the
screw on the solenoid. The maximum pressure of the gas to the burner will
be equal to the nominal delivery pressure minus the head loss within the
gas valve.
[1 mbar = 10,197 mmc.a.]
5. GAS ADJUSTMENTS
Lower Wobbe Index (15°C;1013mbar) MJ/m
3
h
Nominal Delivery Pressure mbar
Minimum Delivery Pressure mbar
21 RFFI
Main Burner: n. 12 jets (ø)mm
Consumption (15°C; 1013mbar) m
3
/h
Consumption (15°C; 1013mbar) Kg/h
Gas Burner Pressure:
max - min mbar
28 RFFI
Main Burner: n. 14 jets (ø)
Consumption (15°C; 1013mbar) m
3
/h
Consumption (15°C; 1013mbar) Kg/h
Gas Burner Pressure:
max - min mbar
CATEGORY II2H3+ Methane Gas
G20
Liquid Butane Gas
G30
Liquid Propane Gas
G31
45.67
20
17
1.30
2.4 - 1.05
----
8.5 - 1.7
1.30
3.15 -1.26
----
11.0 - 1.6
80.58
29
20
0.77
----
1.78 - 0.78
27.5 - 6.2
0.77
----
1.78 - 0.78
27.7 - 4.6
80.58
37
25
0.77
----
1.76 - 0.77
37.4 - 8.0
0.77
----
1.76 - 0.77
35.5 - 6.0
VG002Ab
TABLE 5.1
F
IG. 5.1