InRow SC Operation20
Network Configuration
The cooling unit is shipped with a Network Management Card that enables the cooling unit to be
managed over a network. Configure the network settings for the Network Management Card for this
cooling unit from the display interface. The management card allows remote control and configuration
of the equipment.
Configure network
Path: Main > Configure Network
MAC Address.
Displays the unique network identifier assigned to each equipment at the factory.
Boot Mode. Set the method by which the cooling unit’s Network Management Card will acquire its
network settings.
• Manual: With Manual boot mode selected, enter the IP Address, Subnet Mask, and Default
Gateway using the IP Address menu shown below.
• BOOTP: Set the Network Management Card to obtain its network settings from a BOOTP server.
• DHCP: Set the Network Management Card to obtain its network settings from a DHCP server.
• BOOTPDHCP: Set the Network Management Card to search for its network settings from either
a BOOTP or a DHCP server.
IP Address. You will be prompted to enter the Admin password. Enter the password and press ENTER to
return to the IP screen. Press
ENTER again to change the network settings for Manual boot mode only:
• IP: Enter the IP address assigned to the Network Management Card of this cooling unit.
• SM: Enter the subnet mask for the Network Management Card of this cooling unit.
• GW: Enter the default gateway for the Network Management Card of this cooling unit.
By default, DHCP requires an APC cookie before it will accept an IP address. See
“DHCP” on page 29 for more information.