9.4 SettingthemaximumowwatertemperaturewithOn/Off-control
P101 = 0
Setting the maximum ow water temperature with connected outdoor sensor T4 (starting
with illuminated display):
1. Press the right arrow button:
The display shows: Basic Settings;
2. Press the OK button;
3. Press the right arrow button until CH temp:
The display shows: CH temp 85°C;
4. Press the + or - button to adjust the desired ow temperature and press the OK but-
ton.
Setting the maximum ow water temperature without outdoor sensor T4 (starting with
illuminated display):
1. Press the right arrow button until Timeprog-options;
2. Press the OK button;
3. Press the right arrow button until Timeprog CH;
4. Press the OK button;
5. Press the right arrow button until Day Temp;
6. Press the OK button;
The display shows: T_day
7. Press the + or - button to adjust the desired ow temperature and press the OK but-
ton.
Basic
Settings
CH temp
85 °C
Timeprog
options
Timeprog
CH
Day
Temp
T_day
85 °C