Amana S)8 Furnace User Manual


 
8
L
OCATION
R
EQUIREMENTS
AND
C
ONSIDERATIONS
A copy of the CAN/CSA B149 Installation Codes can also be
obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved method
or in accordance with “ASHRAE Guide” or “Manual J-Load Cal-
culations” published by the Air Conditioning Contractors of
America.
In the USA, this furnace MUST be installed in accordance with
the latest edition of the ANSI Z223.1 booklet entitled “National
Fuel Gas Code” (NFPA 54), and the requirements or codes of
the local utility or other authority having jurisdiction. In Canada,
this furnace must be installed in accordance with the current
CAN/CGA-B149.1 & 2 Gas Installation Codes, local plumbing
or waste water codes and other applicable codes. Additional
helpful publications available from the NFPA are, NFPA 90A -
Installation of Air Conditioning and Ventilating System and NFPA
90B - Warm Air Heating and Air Conditioning System.
All venting shall be in accordance with PART 7, Venting of Equip-
ment, of the National Fuel Gas Code, ANSI Z223.1, or appli-
cable local building and/or air conditioning codes. These pub-
lications are available from:
National Fire Protection Association, Inc.
1 Batterymarch Park, Quincy, MA 02269
NOTE: Furnaces with NOx screens meet the California NOx
emission standards and California seasonal efficiency stan-
dards. ANNUAL inspections of the furnace and its vent system
is strongly recommended.
L
OCATION
R
EQUIREMENTS
AND
C
ONSIDERATIONS
Your unit model type determines which installation procedures
must be used. For *MH8, *MS8, and GHS8 models, you must
follow instructions for Horizontal Left, Horizontal Right or Up-
flow installations only. These furnaces are not approved for
Downflow installations.
Downflow models GD(H,S) ARE NOT APPROVED FOR HORI-
ZONTAL OR UPFLOW INSTALLATIONS. For these models,
use only the instructions for downflow installation only.
T
O
PREVENT
POSSIBLE
EQUIPMENT
DAMAGE
,
PROPERTY
DAMAGE
,
PERSONAL
INJURY
OR
DEATH
,
THE
FOLLOWING
BULLET
POINTS
MUST
BE
OBSERVED
WHEN
INSTALLING
THIS
UNIT
.
WARNING
Follow the instructions listed below when selecting a furnace
location. Refer also to the guidelines provided in Section V,
Combustion and Ventilation Air Requirements.
Centrally locate the furnace with respect to the
proposed or existing air distribution system.
Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.
If the furnace is installed in an application where the
typical operating sound level of a furnace is deemed
objectionable, an optional sound reduction kit is
available. Consult your local distributor for more details.
Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in
locating the furnace.
Ensure adequate combustion air is available for the
furnace. Improper or insufficient combustion air can
expose building occupants to gas combustion products
that could include carbon monoxide. Refer to Section
V, Combustion and Ventilation Air Requirements.
The furnace must be level. If the furnace is to be set
on a floor that may become wet or damp at times, the
furnace should be supported above the floor on a
concrete base sized approximately 1-1/2" larger than
the base of the furnace.
Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material. The only combustible material allowed is
wood.
Exposure to contaminated combustion air will result
in safety and performance-related problems. Do not
install the furnace where the combustion air is exposed
to the following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
If the furnace is used in connection with a cooling unit,
install the furnace upstream or in parallel with the
cooling unit coil. Premature heat exchanger failure
will result if the cooling unit coil is placed ahead of the
furnace.
If the furnace is installed in a residential garage,
position the furnace so that the burners and ignition
source are located not less than 18 inches (457 mm)
above the floor. Protect the furnace from physical
damage by vehicles.
If the furnace is installed horizontally, the furnace
access doors must be vertical so that the burners fire
horizontally into the heat exchanger. Do not install
the unit with the access doors on the “up/top” or “down/
bottom” side of the furnace.