4.2.2 Zone or Point Supervisory
A zone or point must be defined as supervisory to allow the ADT-UDACT to identify
the correct report to transmit to the central station. Follow the programming
instructions in the FACP manual to program a zone or point as supervisory. Next,
program the zone or point as a code 2 for supervisory. Use the charts in Appendices
to enter point and zone definitions. Note that the ADT-UDACT fire protection and
reporting capabilities are inactive while in Type Mode.
To get into the Troubleshoot Mode, press MODE 8768 and [ENTER/STORE].
8768 spells TROU on a Touch-Tone® phone.
Once in this mode, the ADT-UDACT will:
• Transmit the 'UDACT off normal' message to the Central Station(s).
Continue to communicate any events not yet acknowledged at the
Central Station prior to entering Troubleshoot Mode.
The UP Arrow key, Down Arrow key and 1st EVENT keys do not function in
this mode.
Telephone Line Testing
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/
STORE] causes seizure of the Primary phone line which in turn lights the red
LED signifying Primary phone line active. After a delay of three seconds, the
ADT-UDACT goes off hook to acquire a dial tone.
The ADT-UDACT keypad may be used as a telephone touchpad for number dialing.
Once the first digit is pressed, the display will move the C or D character one
position to the left, while placing the digit to be dialed on the farthest right display
position. Continue to press the phone numbers to be dialed. Successive depressions
of the [ENTER/STORE] key hangs up and picks up the phone (places the phone on
or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing
or the F key for rotary dialing and then following the same procedure used for the
primary phone line.
A handset may be temporarily connected across transformer T1 as indicated in Figure
4-2. The handset, when connected across T1, may be used only as an amplifier/
speaker or telephone with the ADT-UDACT used for number dialing.
4.3 Troubleshoot
Mode