ADT Security Services ADT-UDACT Home Security System User Manual


 
Document 50934 Rev B 5/15/00 PN 50934:B
34
For all pulsed formats and both Ademco Express formats, the zone/point report is
repeated per the total number of zones or points activated once factory default entries
of zero are removed. See Tables 3-2, 3-3, 3-4, 3-5, 3-6 and 3-7. When Ademco Contact
ID format is used, the actual zone or point activated is identified in the report.
The ADT-UDACT comes factory programmed with the reports identified above as item
numbers 2, 4, 7, 20, 22 and 25 set to zero, preventing the reports from being transmitted
for the pulsed and Ademco Express formats. These reports are factory programmed for
active transmission when using the Ademco Contact ID.
4.1.4 Key Report Descriptions
ADT-UDACT OFF Normal Report
Removing the ADT-UDACT from Normal Mode and placing it into Program or
Troubleshoot Mode causes a transmission of an 'UDACT off normal' fault message.
Returning the ADT-UDACT to Normal Mode causes a transmission of a 'UDACT return
to normal' restoral message.
Panel OFF Normal Report
The ADT-UDACT will report a "System off normal" report when the host FACP
temporarily shuts down the EIA-485 communications bus during various aspects of system
programming. When the host FACP is returned to normal, restoring the fire protection,
the ADT-UDACT will report a 'system off normal restoral' report.
System Test Report
The ADT-UDACT will transmit a test message to both Central Stations at programmed
intervals (typically every 24 hours). Should there exist an abnormal condition in the fire
alarm system (such as an alarm, trouble or supervisory condition) at the time when the test
report is due to be transmitted, the ADT-UDACT will report the 'system abnormal test
report.' If the system is normal, the report transmitted will be the normal 'system test
report.'
EIA-485 Communications Trouble Report
The ADT-UDACT supervises the integrity of the information received from the FACP via
the EIA-485 communications bus. Should the communications bus malfunction or be
temporarily disabled, the ADT-UDACT transmits the report '485 comm trouble.' When
the communications bus returns to proper operation, the ADT-UDACT will report '485
comm trouble restoral.'
Type Mode may be used to disable reports by zone or point and to identify the specific
functionality of each zone or point in the system via Ademco Contact ID format. Factory
default for all zones is Fire Alarm. When reporting point information, the factory default
for addressable monitor modules is Fire Alarm code 110 and the default for addressable
detectors is Smoke Detector code 111. The smoke detector default cannot be modified.
Use Type Mode to identify the function of each zone or point as follows:
• General fire alarm • Burglary
• Supervisory • 24 hour non-burglary
• Pull stations • High temperature
• Heat detectors • Low temperature
• Waterflows • Low water pressure
• Duct detectors • Low water level
• Flame sensor • Pump failure
• Smoke zone
Note: Unimode 2020/1010 and ADT-MNNA applications restrict Type Mode program-
ming to a maximum of 568 points. All remaining points above 568 will report as fire
alarm points.
4.2 Type Mode