ADT Security Services ADT-UDACT Home Security System User Manual


 
Document 50934 Rev B 5/15/00 PN 50934:B
24
Programming the Real-Time Clock
Entering an address greater than 209 will cause a display of the current time. On
initial power up, the clock will start running from the factory setting of 00:01
(military time). The far left digit will be flashing, indicating that this is the first digit
to be programmed.
Hours/Minutes
Select a digit then press [ENTER/STORE]. The digit 2nd from the left will start
flashing. Select a digit then press [ENTER/STORE]. Hours setting is complete.
With the digit 2nd from the right flashing, select a digit then press [ENTER/
STORE]. The digit on the far right will start flashing. Select a digit then press
[ENTER/STORE]. Minutes setting is complete.
End Programming
Exit Programming Mode by pressing MODE, followed by the 4-digit code
corresponding to an alternate mode of operation, then press [ENTER/STORE].
During Program Mode, if no key is pressed within 10 minutes, the ADT-UDACT will
revert to normal mode.
Table 3-2: Event Codes, Primary Number
3+1, 4+1 Express and 4+1 Standard Formats If '0, 2, 4, 6 or 8' are entered for
address 16, the following data is automatically programmed for the Primary phone
number event codes. Enter a '0' for the data setting to disable the report. These
formats do not support zone/point programming. For zone/point reporting, refer to
Contact ID.
Address Description Setting
69 Primary # General Alarm Code 1
70 Primary # Zone/Point Alarm Code 0
71 Primary # General Supervisory Code 8
72 Primary # Zone/Point Supervisory Code 0
73 Primary # General Fault Code F
74 Primary # AC Fault Code F
75 Primary # Zone/Point Fault Code 0
76 Primary # Low Battery Fault Code F
77 Primary # Telco Primary Line Fault Code F
78 Primary # Telco Secondary Line Fault Code F
79 Primary # NAC Fault Code F
80 Primary # Comm. Trouble Primary # Code F
81 Primary # Comm. Trouble Secondary # Code F
82 Primary # 485 Comm. Trouble Code F
83 Primary # System Off Normal Code F
84 Primary # ADT-UDACT Off Normal Code F
85 Primary # General Alarm Restore Code E
86 Primary # Zone/Point Alarm Restore Code 0
87 Primary # General Supervisory Restore Code E
88 Primary # Zone/Point Supervisory Restore Code 0
89 Primary # General Fault Restore Code E
90 Primary # AC Fault Restore Code E
91 Primary # Zone/ Point Fault Restore Code 0
92 Primary # Low Battery Fault Restore Code E
93 Primary # Telco Primary Line Fault Restore Code E
94 Primary # Telco Secondary Line Fault Restore Code E
95 Primary # NAC Fault Restore Code E
96 Primary # Comm.Trouble Primary Number Restore Code E
97 Primary # Comm. Trouble Secondary Number Restore Code E
98 Primary # 485 Comm. Trouble Restore Code E
99 Primary # System Off Normal Restore Code E
100 Primary # ADT-UDACT Off Normal Restore Code E
101 Primary # System 24 Hour Test 9
102 Primary # System 24 Hour Test w/active event F
103 Primary # Manual Test 9
Note: Zero entries prevent the transmission of the report to the Central Station.