W WARNING
GENERAL SAFETY INFORMATION
Intended Use
The 3M™ Macurco™ GD-6 Combustible Gas Detector, Controller and Transducer is a low voltage device with selectable 4-20mA
output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of combustible
gas and provide feedback and automatic exhaust fan control to help reduce combustible gas concentrations in parking garages,
maintenance facilities or other light commercial applications. The 3M™ Macurco™ GD-6 Combustible Gas Detector is a low level
meter capable of displaying from 0-50% LEL (Lower Explosive Limit) of combustible gas. The 3M™ Macurco™ GD-6 Combustible
Gas Detector is factory calibrated and tested for proper operation, but can also be calibrated in the field.
List of Warnings and Cautions within these User Instructions
USE INSTRUCTIONS AND LIMITATIONS
W WARNING
W WARNING
•Eachpersonusingthisequipmentmustreadandunderstandtheinformationinthese User Instructions before use. Use
ofthisequipmentbyuntrainedorunqualiedpersons,orusethatisnotinaccordancewiththeseUser Instructions, may
adversely affect product performance and result in sickness or death.
•Useonlyformonitoringthegaswhichthesensorandinstrumentaredesignedtomonitor.Failuretodosomayresultin
exposures to gases not detectable and cause sickness or death. For proper use, see supervisor or User Instructions, or
call 3M in U.S.A., 1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.
•GD-6maynotfunctioneffectivelybelow0°Forabove125°F(-18°Corabove52°C).Usingthedetectoroutsideofthis
temperature range may adversely affect product performance and result in sickness or death.
•Thisdetectorhelpsmonitorforthepresenceandconcentrationlevelofcertainspeciedairbornegases.Misusemay
produce an inaccurate reading, which means that higher levels of the gas being monitored may be present and could
result in overexposure and cause sickness or death. For proper use, see supervisor or User Instructions, or call 3M in
U.S.A., 1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.
•Eachtimetheunitisturnedonitperformsaself-test,whichactivatesvisualalarms.Iftheself-testfails,orifallthealarmsdo
not activate, do not use. Failure to do so may adversely affect product performance and result in sickness or death.
•Donotcoverorobstructvisualalarm.Doingsomayadverselyaffectproductperformanceandresult in sickness or death.
•Donotdisassembleunitorattempttorepairormodifyanycomponentofthisinstrument.Thisinstrumentcontainsnouser
serviceable parts, and substitution of components may impair product performance and result in sickness or death.
•Usingacertiedgaswithaconcentrationotherthantheonelistedforthisinstrumentandsensorwhenconductinga
calibration or calibration verification test (bump test) will produce inaccurate readings. This means that higher levels of the
gas being monitored may be present and could result in overexposure and cause sickness or death. For proper use, see
supervisor, User Instructions or call 3M in U.S.A., 1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.
•Thefollowingstepsmustbeperformedwhenconductingacalibrationorcalibrationvericationtest(bumptest)toensureproper
performance of the monitor. Failure to do so may adversely affect product performance and result in sickness or death.
• Whenperformingacalibrationorcalibrationvericationtest(bumptest)onlyusecertiedcalibrationgasatthe
requiredconcentrationlevel.Donotcalibratewithexpiredcalibrationgas.
• Iftheinstrumentcannotbecalibrated,donotuseuntilthereasoncanbedeterminedandcorrected.
• Donotcoverorobstructdisplayorvisualalarmcover.
• Ensuresensorinletisunobstructedandisfreeofdebris.
EachpersonusingthisequipmentmustreadandunderstandtheinformationintheseUser Instructions before use. Use
ofthisequipmentbyuntrainedorunqualiedpersons,orusethatisnotinaccordancewiththeseUser Instructions, may
adversely affect product performance and result in sickness or death.
Use For
The 3M™ Macurco™ GD-6 Combustible Gas Detector helps combustible gas detection and automatic exhaust fan control
for automotive maintenance facilities, enclosed parking garages, warehouses with forklifts, etc. The 3M™ Macurco™ GD-6
Combustible Gas Detector can be used with 12VDC or 24VDC N.O. (fire/security) panels.
Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do so may result in
exposures to gases not detectable and cause sickness or death. For proper use, see supervisor or User Instructions, or
call 3M in U.S.A., 1-800-243-4630. In Canada, call Technical Service at 1-800-267-4414.
W WARNING
Do Not Use For
The 3M™ Macurco™ GD-6 Combustible Gas Detector is NOT intended for use in hazardous locations or industrial applications
such as refineries, chemical plants, etc.
DO NOTmountthe3M™Macurco™GD-6CombustibleGasDetectorwherethenormalambienttemperatureisbelow0°For
exceeds125°F(-18°Corabove52°C).The3M™Macurco™GD-6CombustibleGasDetectormountsonatype4Selectrical
box supplied by the contractor.
The3M™Macurco™GD-6CombustibleGasDetectormaynotfunctioneffectivelybelow0°Forabove125°F(-18°Cor
above52°C).Usingthedetectoroutsideofthistemperaturerangemayadverselyaffectproductperformanceand result in
sickness or death.
General Description
The 3M™ Macurco™ GD-6 Combustible Gas Detector is a low voltage, dual relay combustible gas (EX) detector and automatic
ventilation controller. The 3M™ Macurco™ GD-6 Combustible Gas Detector uses a microcomputer controlled, electronic
system to measure the concentration of combustible gas, actuate relays and provide a 4-20mA (0-50% LEL) output. The
3M™ Macurco™ GD-6 Combustible Gas Detector is low maintenance with a long life (5+ years) pellistor sensor and optional
gas test and calibration kits. The 3M™ Macurco™ GD-6 Combustible Gas Detector is a low level meter capable of displaying
from 0-50% LEL of combustible gas.