DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009 Specifications Page 173
17 Appendix 2 - Specifications
Universal Process Input
General Input Specifications
Ten samples per second.
time constant
0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.
Always four times better than display resolution. 16 bit ADC.
Influence:
Negligible effect on readings within the specified supply voltage
tolerances.
Influence:
Negligible effect on readings within the specified humidity tolerance.
Stability:
0.01% of span/C change in ambient temperature.
V DC: 47KΩ
mA DC: 5Ω
Other ranges:
Greater than 10M resistive
Isolated from all outputs (except SSR Drivers) at 240V AC
Adjustable input span. +ve values are added to Process Variable, -ve
values are subtracted from Process Variable
Displays process variable up to 5% over and 5% under span.
Thermocouple Input
Thermocouple Types & Ranges
Type
Range in
C Range in
F
Type
Range in
C Range in
F
B
100 to 1824°C 211 to 3315°F
L
0 to 762°C 32 to °F
C
0 to 2315°C 32 to 4199°F
N
0 to 1399°C 32 to 2551°F
D
0 to 2320°C 32 to 4208°F
PtRh20%:
PtRh40%
0 to 1850°C 32 to 3362°F
E
-240 to 1000°C -400 to 1832°F
R
0 to 1759°C 32 to 3198°F
J (default)
-200 to 1200°C -328 to 2192°F
S
0 to 1762°C 32 to 3204°F
K
-240 to 1373°C -400 to 2503°F
T
-240 to 400°C -400 to 752°F
Note:
Defaults to °F for USA units. Defaults to °C for non-USA units.
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to
restrict range. An optional decimal place can be displayed up to 999.9°C/F