DCP200 Profile Controller & Recorder - Product Manual
51-52-25-150, Issue 1 – April 2009 Modbus Parameters Page 107
1 Start Recording
Data Recorder
Fitted
7553 0x1D81 RO
0 Not Fitted
1 Recorder Fitted
Memory Remaining 7554 0x1D82 RO Memory unused remaining left, in bytes
Time Remaining 7555 0x1D83 RO Time remaining until memory is used up, in seconds
Recorder Trigger 7563 0x1D8B R/W
0 Operator start/stop
1 Recorder Menu start/stop
2
3 Digital input A
4 Digital input B
5 During running of profiles
Record Process
Variable
7572 0x1D94 R/W
0 Do Not Record PV
1 Record PV Value
Record Maximum
PV Between
Samples
7573 0x1D95 R/W
Record Max PV Since Last Sample
0 Do Not Record Maximum PV
1 Record Maximum PV Between Samples
Record Minimum PV
Between Samples
7574 0x1D96 R/W
Record Min PV Since Last Sample
0 Do Not Record Minimum PV
1 Record Minimum PV Between Samples
Record Actual
Setpoint
7575 0x1D97 R/W
Record Actual Setpoint Value
0 Do Not Record Setpoint
1 Record Actual Setpoint
Record Primary
Power
7576 0x1D98 R/W
Record Primary Power Value
0 Do Not Record Primary Power
1 Record Primary Power
Record Secondary
Power
7577 0x1D99 R/W
Record Secondary Power Value
0 Do Not Record Secondary Power
1 Record Secondary Power
Record Alarm 1
Status
7578 0x1D9A R/W
Record Change Of State For Alarm 1
0 Do Not Record Alarm 1
1 Record Alarm 1
Record Alarm 2
Status
7579 0x1D9B R/W
Record Change Of State For Alarm 2
0 Do Not Record Alarm 2
1 Record Alarm 2
Record Alarm 3
Status
7580 0x1D9C R/W
Record Change Of State For Alarm 3
0 Do Not Record Alarm 3
1 Record Alarm 3
Record Alarm 4
Status
7581 0x1D9D R/W
Record Change Of State For Alarm 4
0 Do Not Record Alarm 4
1 Record Alarm 4