Reference manual Foundation Fieldbus Control module
DOC.RM.QC34.E Rev: A
October, 2006
Name Description Valid Range Initial Value Permission
1 ST_REV Static data revision. Updated when static data is changed 0 to 65535 0 Read only
2 TAG_DESC Unique description for the resource block within a system,
writable by the host system operator.
spaces Read / Write
3 STRATEGY Used by host system administrator to group blocks foe easy
identification of location.
7 bit ASCII 0 Read / Write
4 ALERT_KEY Plant unit ID, for host system operator for sorting alarms 1 to 255 0 Read / Write
5 MODE_BLK The target, actual and permitted modes for the block
TARGET OOS, IMAN,
AUTO
AUTO Read / Write
ACTUAL N/A Read Only
PERMITTED ALL Read / Write
NORMAL AUTO Read / Write
6 BLOCK_ERR Error status associated with the hardware or software of the
resource block
0 to F N/A Read Only
0: Other
1: Block config error (not used)
2: Link configuration error
3: Simulate Active: Based on switch
4: Local override (not used)
5: Device Fail safe set
6: Device needs Maintenance Soon
7: Input failure (not used)
8: Output failure (not used)
9: Memory Failure (FF card)
10: Lost static data (FF card)
11:Lost NV data (FF card)
12: Readback check failed (not used)
13: Device needs Maintenance Now
14: Power-up (not used)
15: Out-of-Service
7 RS_STATE State of the resource 1 to 6 5 Read only
1: Start restart
2: Initialization, actual mode = IMAN
3: Online linking
4: Online, actual mode = Auto
5: Standby
6: Failure
8 TEST_RW Read write test parameter for interoperability testing Not applicable Not
applicable
Not applicable
9 DD_RESOURCE Tag ID string identifying DD resource for info only spaces Read only
10 MANUFAC_ID Manufacturing identification number, used by an interface
device to locate DD file for resurce. Should show up as Valve
automation
0xA2C1 0xA2C1 Read only
11 DEV_TYPE Manufacturers model number 0xD3A0 = FieldQ – Pneumatic
Valve Actuator
0xD3A0 0xD3A0 Read only
12 DEV_REV Used to locate DD file set to: 2 2 2 Read only
13 DD_REV Minimum compatible DD revision number associated with this
device
2 2 Read only
14 GRANT_DENY Access control to host computer. Valid settings: 0
Program, 1 Tune,
2 Alarm, 3 Local
GRANT
DENY
15 HARD_TYPES The types of hardware available as channel numbers on this
resource
0 Scalar Input, 1
Scalar output, 2
Discrete Input, 3
Discrete Output
Read only
16 RESTART Shows current status and allows a manual restart to be
initiated, implemented as method with warnings!
1 Run - Normal operation
2 Resource - Restart FF resource keep settings.
3 Defaults - Restart FF resource with default.
4 Processor - Restart FF Resource.
5 Actuator defaults - Restart control module with factory
settings
6 Actuator processor - Restart control module, keep settings.
Table 4.1 FieldQ™ Resource Block
Index
No.
1 to 6 1 Read only
0x00 Read / Write