Reference manual Foundation Fieldbus Control module
DOC.RM.QC34.E Rev: A
October, 2006
Control Module
Type Label
Terminals
Status LED
M127/8" UNC
1
2
3
4
1
2
3
4
1
2
3
1
2
4
Electrical Connections
Signal Internal Quick connector
terminal nr nr color
FF signal - 1 2 Blue
Shield 2 4 Green / Yellow
FF signal + 3 1 Brown
3 Not connected
Fig. 2.5.3Terminal and quick connector connections
Quick connector pinouts:
(male chassis part)
Fig. 2.5.4Quick connector pinouts
Fig. 2.5.1Installing wiring
WARNING:
* Do not put the Control module and the
Pneumatic module in direct contact with
magnetic material. This can cause damage
or malfunction of the position feedback.
* If the Control module is used in a manner
not specified by the manufacturer, the
protection provided by the equipment may
be impaired.
* If required, mount earth wire (1) between
top (2) and bottom (3) ring of earth wire
connection (see figure 2.5.2).
2.5.5 Procedure
1 Remove control module cover (see figure 2.5.1)
2 Guide the cable(s) through the electrical entry(ies).
- Use and mount cable glands as required by
national or local legislation.
- When IP65/NEMA4X ingress protection is
required, the electrical entries must be fitted with
glands rated IP65/NEMA4X or higher.
3 Connect the FOUNDATION™ Fieldbus signal to
the applicable terminals (see figure 2.53).
- For 7/8” or M12 quick connector pinout, see fig 6.
- For hazardous area connections, see the control
drawings as indicated in chapter 2.5.2.
4 Mount the control module cover to the housing
(see figure 2.5.1) or continue with chapter 3. Take
care that the cover seal is in place to comply to
dust and water tightness according IP65 /
NEMA4X.
2.5.6 FOUNDATION Fieldbus™ installation and
wiring guidelines
For various application guides like installation and
wiring guidelines please check:
www.fieldbus.org/About/FoundationTech/Resources/
Fig.2.5.2 Earth wire connection