York YZB018 THRU 060 Air Conditioner User Manual


 
271457-YTG-B-0908
34 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
Continued on Page 35.
HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YZB03011
INDOOR COIL MODEL NO. FC/MC/PC/UC36
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
800 1000 1200
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 34.3 2.5 4.0 35.3 2.4 4.4 36.3 2.2 4.8
70 33.3 2.8 3.5 34.3 2.6 3.8 35.3 2.5 4.2
80 32.3 3.1 3.1 33.3 2.9 3.4 34.3 2.7 3.7
47
60 29.8 2.4 3.6 30.7 2.3 3.9 31.5 2.2 4.3
70 29.3 2.7 3.2 30.0 2.6 3.4 30.7 2.4 3.7
80 28.8 3.0 2.8 29.3 2.8 3.1 29.9 2.6 3.3
40
60 27.7 2.4 3.4 28.6 2.3 3.7 29.5 2.2 4.0
70 27.1 2.7 3.0 27.9 2.6 3.2 28.7 2.4 3.5
80 26.6 3.0 2.6 27.2 2.8 2.8 27.8 2.7 3.1
30
60 22.3 2.2 2.9 23.7 2.2 3.2 25.1 2.1 3.5
70 22.0 2.5 2.6 23.3 2.4 2.9 24.6 2.3 3.1
80 21.7 2.7 2.4 22.9 2.6 2.6 24.1 2.6 2.8
17
60 17.2 2.2 2.3 18.2 2.1 2.5 19.2 2.1 2.7
70 17.4 2.4 2.1 18.3 2.4 2.3 19.2 2.3 2.4
80 17.6 2.7 1.9 18.4 2.6 2.1 19.1 2.5 2.2
10
60 16.4 2.1 2.3 17.2 2.1 2.4 18.0 2.1 2.5
70 15.9 2.4 2.0 16.7 2.3 2.1 17.5 2.3 2.3
80 15.4 2.6 1.7 16.2 2.6 1.9 17.0 2.5 2.0
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil MBH KW COP
MA12B FC/MC36B 1.00 1.00 1.00
MV12B FC/MC36B 0.98 0.98 1.00
MV16C FC/MC36C 0.98 0.98 1.00
AHP30 1.00 1.00 1.00
AHP36 1.00 1.00 1.00
AV36 0.97 0.91 1.06
F*FP036 0.99 0.99 1.00
HC36 1.00 1.00 1.00