York YZB018 THRU 060 Air Conditioner User Manual


 
271457-YTG-B-0908
Johnson Controls Unitary Products 23
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. YZB01811
INDOOR COIL MODEL NO. FC/MC/PC/UC18
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 14.4 17.2 16.4 18.9 21.3 16.8 19.1 18.1 20.7 22.2 19.2 20.9 19.8 22.6 23.1
S.C. 14.5 12.8 10.6 11.1 9.0 16.9 15.4 12.7 13.1 10.1 19.4 18.1 14.9 15.1 11.2
KW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
75
T.C. 13.9 16.5 15.8 18.2 20.2 16.0 18.1 17.4 19.8 21.1 18.2 19.8 18.9 21.5 22.0
S.C. 14.0 12.4 10.3 10.7 8.6 16.1 14.9 12.5 12.7 9.7 18.3 17.4 14.6 14.7 10.8
KW 1.3 1.3 1.3 1.3 1.2 1.3 1.3 1.3 1.3 1.2 1.3 1.3 1.3 1.2 1.2
85
T.C. 13.3 15.7 15.3 17.4 19.0 15.2 17.2 16.7 18.9 19.9 17.1 18.6 18.1 20.4 20.8
S.C. 13.4 12.1 10.1 10.4 8.1 15.3 14.4 12.2 12.4 9.3 17.2 16.8 14.2 14.3 10.4
KW 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
95
T.C. 12.7 14.9 14.7 16.7 17.9 14.4 16.2 15.9 18.0 18.8 16.1 17.5 17.2 19.3 19.7
S.C. 12.8 11.8 9.9 10.1 7.7 14.5 13.9 11.9 12.0 8.9 16.1 16.1 13.9 13.9 10.0
KW 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6
105
T.C. 12.2 14.1 13.8 15.7 16.9 13.8 15.5 14.9 16.9 17.7 15.4 16.8 16.1 18.1 18.5
S.C. 12.3 11.5 9.6 9.7 7.3 13.9 13.5 11.4 11.5 8.4 15.4 15.5 13.3 13.4 9.5
KW 1.9 1.9 1.8 1.9 1.8 1.9 1.9 1.8 1.8 1.8 1.9 1.8 1.8 1.8 1.8
115
T.C. 11.7 13.4 12.9 14.7 15.9 13.2 14.8 13.9 15.8 16.6 14.7 16.1 15.0 16.9 17.3
S.C. 11.8 11.3 9.2 9.3 7.0 13.3 13.0 11.0 11.1 8.0 14.8 14.8 12.7 12.9 9.0
KW 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1
125
T.C. 11.2 12.7 11.9 13.8 14.8 12.6 14.1 12.9 14.7 15.5 14.1 15.5 13.9 15.7 16.1
S.C. 11.3 11.0 8.9 8.9 6.6 12.7 12.6 10.5 10.6 7.5 14.1 14.2 12.2 12.3 8.4
KW 2.4 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
MA08B FC/MC18B 1.00 1.00 1.00
MV12B FC/MC18B 0.97 0.98 0.96
AHP18 1.00 1.00 1.00
AV24 1.00 0.98 0.96
F*FP024 0.99 1.00 1.00
HC18 1.00 1.00 1.00
HD24 1.00 1.00 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*A12 FC/MC/PC18A 1.02 0.97 1.07
PV9*A12 FC/MC/PC18A 1.01 0.97 1.07
P(C,V)9*B12 FC/MC/PC18B 1.01 0.97 1.07
Y*(8,L)C*A12 FC/MC/PC18A 1.00 1.02 0.92
Y*(8,L)C*B12 FC/MC/PC18B 1.00 1.00 0.91
Y*9C*B12 FC/MC/PC18B 1.00 1.01 0.91
Y*(8,L)C*A12 FC/MC/PC24A 1.00 1.04 0.92
Y*(8,L)C*B12 FC/MC/PC24B 1.00 1.00 0.90
Y*9C*B12 FC/MC/PC24B 1.00 1.04 0.91
Y*(8,L)C*A12 FC/MC/PC30A 1.00 1.04 0.92
Y*(8,L)C*B12 FC/MC/PC30B 1.00 1.00 0.90
Y*9C*B12 FC/MC/PC30B 1.00 1.04 0.91
Y*(8,L)C*A12 HC18 1.00 1.02 0.92
Y*(8,L)C*A12 HD24 1.00 1.03 0.92
Y*(8,L)C*B12 HD24 1.00 1.00 0.90
Y*9C*B12 HD24 1.00 1.03 0.91
Y*(8,L)C*A12 UC18A 1.00 1.02 0.92
Y*(8,L)C*B12 UC18B 1.00 1.00 0.91
Y*9C*B12 UC18B 1.00 1.02 0.91
Y*(8,L)C*A12 UC24A 1.00 1.04 0.92
Y*(8,L)C*B12 UC24B 1.00 1.01 0.90
Y*9C*B12 UC24B 1.00 1.04 0.91
Y*(8,L)C*A12 UC30A 1.00 1.04 0.92
Y*(8,L)C*B12 UC30B 1.00 1.01 0.90
Y*9C*B12 UC30B 1.00 1.04 0.91
G*9V*A12 FC/MC/PC18A 1.00 1.02 0.93
G*9V*B12 FC/MC/PC18B 1.00 1.01 0.91
G*9V*A12 FC/MC/PC24A 1.00 1.03 0.93
G*9V*B12 FC/MC/PC24B 1.00 1.04 0.91
G*9V*A12 FC/MC/PC30A 1.00 1.03 0.93
G*9V*B12 FC/MC/PC30B 1.00 1.04 0.91
G*9V*A12 HC18 1.00 1.02 0.93
G*9V*A12 HD24 1.00 1.02 0.93
G*9V*B12 HD24 1.00 1.03 0.91
G*9V*A12 UC18A 1.00 1.03 0.93
G*9V*B12 UC18B 1.00 1.02 0.91
G*9V*B12 UC24B 1.00 1.04 0.91
G*9V*A12 UC30A 1.00 1.03 0.93
G*9V*B12 UC30B 1.00 1.04 0.91
Variable Speed
Furnace
Coil T.C. S.C. KW