York YCUL0130 Fan User Manual


 
YORK INTERNATIONAL
108
YORK INTERNATIONAL
109
FORM 150.63-EG1
SYSTEM #1 COMPRESSOR & FAN
COMPR. #1 COMPR. #2 COMPR. #3 FANS
RLA LRA RLA LRA RLA LRA QTY FLA(EA)
100.2 550 100.2 550 3 8.2
92.8 550 92.8 550 3 7.8
53.5 305 53.5 305 3 4.8
44.2 270 44.2 270 3 4.0
35.4 210 35.4 210 3 3.1
100.2 550 100.2 550 3 8.2
92.8 550 92.8 550 3 7.8
53.5 305 53.5 305 3 4.8
44.2 270 44.2 270 3 4.0
35.4 210 35.4 210 3 3.1
73.9 450 73.9 450 73.9 450 4 8.2
68.5 450 68.5 450 68.5 450 4 7.8
39.5 260 39.5 260 39.5 260 4 4.8
32.6 215 32.6 215 32.6 215 4 4.0
26.1 180 26.1 180 26.1 180 4 3.1
73.9 450 73.9 450 73.9 450 4 8.2
68.5 450 68.5 450 68.5 450 4 7.8
39.5 260 39.5 260 39.5 260 4 4.8
32.6 215 32.6 215 32.6 215 4 4.0
26.1 180 26.1 180 26.1 180 4 3.1
100.2 550 100.2 550 100.2 550 4 8.2
92.8 550 92.8 550 92.8 550 4 7.8
53.5 305 53.5 305 53.5 305 4 4.8
44.2 270 44.2 270 44.2 270 4 4.0
35.4 210 35.4 210 35.4 210 4 3.1
SYSTEM #2 COMPRESSOR & FAN
COMPR. #1 COMPR. #2 COMPR. #3 FANS
RLA LRA RLA LRA RLA LRA QTY FLA(EA)
73.9 450 73.9 450 3 8.2
68.5 450 68.5 450 3 7.8
39.5 260 39.5 260 3 4.8
32.6 215 32.6 215 3 4.0
26.1 180 26.1 180 3 3.1
100.2 550 100.2 550 3 8.2
92.8 550 92.8 550 3 7.8
53.5 305 53.5 305 3 4.8
44.2 270 44.2 270 3 4.0
35.4 210 35.4 210 3 3.1
100.2 550 100.2 550 4 8.2
92.8 550 92.8 550 4 7.8
53.5 305 53.5 305 4 4.8
44.2 270 44.2 270 4 4.0
35.4 210 35.4 210 4 3.1
73.9 450 73.9 450 73.9 450 4 8.2
68.5 450 68.5 450 68.5 450 4 7.8
39.5 260 39.5 260 39.5 260 4 4.8
32.6 215 32.6 215 32.6 215 4 4.0
26.1 180 26.1 180 26.1 180 4 3.1
73.9 450 73.9 450 73.9 450 4 8.2
68.5 450 68.5 450 68.5 450 4 7.8
39.5 260 39.5 260 39.5 260 4 4.8
32.6 215 32.6 215 32.6 215 4 4.0
26.1 180 26.1 180 26.1 180 4 3.1
YCUL0096 - YCUL0130
MULTIPLE POINT POWER SUPPLY CONNECTIONS (see Fig. 3)
(Two Field Provided Power Supply Circuits to the condensing unit. Field connections to Factory Provided Terminal Blocks (standard), Non-Fused Disconnect
Switches (optional) or Individual System Circuit Breakers (optional) per electrical system.)