Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature
* = Single-phase outdoor units only.
* = Single-phase outdoor units only.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. EABD-F048S, EABD-(T,W)048S**
INDOOR COIL MODEL NO. FC/MC/PC/UC60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 43.2 47.1 45.4 49.6 51.0 46.2 48.0 45.8 49.7 51.3 49.2 48.8 46.2 49.7 51.6
S.C. 42.7 41.7 34.8 34.3 26.0 43.8 43.3 37.1 36.6 27.7 44.8 44.8 39.4 38.8 29.5
K.W. 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
75
T.C. 43.1 45.5 43.5 47.8 49.9 45.7 46.6 44.0 48.2 50.2 48.3 47.7 44.5 48.6 50.5
S.C. 41.4 40.6 33.9 33.7 25.8 42.6 42.2 36.2 36.0 27.4 43.8 43.7 38.5 38.2 29.0
K.W. 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7
85
T.C. 42.9 43.8 41.6 46.1 48.9 45.2 45.2 42.2 46.8 49.1 47.4 46.5 42.8 47.4 49.3
S.C. 40.1 39.5 33.1 33.1 25.6 41.5 41.0 35.3 35.4 27.1 42.8 42.6 37.5 37.7 28.6
K.W. 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
95
T.C. 42.8 42.1 39.7 44.3 47.9 44.7 43.8 40.4 46.0 48.0 46.5 45.4 41.1 46.3 48.2
S.C. 38.9 38.4 32.2 32.5 25.4 40.4 39.9 34.4 35.4 26.8 41.9 41.4 36.6 37.2 28.1
K.W. 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.4 3.3 3.3 3.3 3.3 3.3
105
T.C. 40.5 40.2 37.6 42.1 45.0 42.6 41.8 38.2 42.9 45.4 44.7 43.4 38.8 43.7 45.7
S.C. 37.1 36.7 31.2 31.7 24.5 38.5 38.2 33.2 34.0 25.9 40.0 39.6 35.2 36.3 27.3
K.W. 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7 3.7
115
T.C. 38.2 38.3 35.5 40.0 42.2 40.6 39.9 36.0 40.6 42.8 43.0 41.4 36.6 41.2 43.3
S.C. 35.4 35.1 30.3 30.9 23.5 36.8 36.5 32.1 33.2 25.0 38.1 37.8 33.9 35.5 26.5
K.W. 4.1 4.1 4.1 4.1 4.1 4.2 4.1 4.1 4.1 4.1 4.2 4.1 4.1 4.1 4.1
125
T.C. 35.9 36.5 33.4 37.9 39.4 38.6 37.9 33.9 38.3 40.2 41.3 39.4 34.4 38.8 40.9
S.C. 33.7 33.5 29.4 30.2 22.6 35.0 34.8 31.0 32.4 24.1 36.3 36.1 32.6 34.7 25.7
K.W. 4.6 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.6 4.6 4.5 4.5 4.5 4.6
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
** For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.
Air Handler Coil
T.C. S.C. KW
MA16C FC60C 1.00 1.00 1.00
MA20D FC/MC60D 1.00 1.00 1.00
MA20D MC61D 1.00 1.00 1.00
AHP/SHP48 1.00 1.00 1.00
AHP/SHP60 1.00 0.98 1.00
F*FV060* 1.00 0.98 0.92
MV20D* FC/MC60D 1.00 0.98 1.00
MV20D* MC61D 1.01 0.98 1.01
AV/SV48* 1.01 0.98 1.01
HC60 0.99 0.97 0.99
HD60 0.98 0.98 0.98
MC61 1.00 1.00 1.00
Variable Speed
Furnace *
Coil
T.C. S.C. KW
FL9(C,V)D20 FC/MC/PC60D 1.00 1.00 1.00
(F,L)L8VC16 FC/PC60C 0.99 0.99 0.99
(F,L)L8VC20 FC/PC60C 1.00 1.00 1.00
FL9(C,V)C16 FC/PC60C 1.00 1.00 1.00
FL9(C,V)C20 FC/PC60C 1.00 0.97 1.00
FL9(C,V)D20 HC60 1.00 1.00 1.00
(F,L)L8VC20 HD60 1.00 1.00 1.00
FL9(C,V)C20 HD60 1.00 0.98 1.00
FL9(C,V)D20 MC61D 1.01 0.99 1.01