York W)036 THRU 060 Heat Pump User Manual


 
246819-BTG-H-0208
20 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
* = Single-phase outdoor units only.
* = Single-phase outdoor units only.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. EABD-F030S, EABD-(T,W)030S**
INDOOR COIL MODEL NO. FC/MC/PC35
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 800 1000 1200
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 28.5 31.9 31.9 34.8 34.4 30.7 32.7 34.5 34.2 33.7 32.9 33.5 37.2 33.6 33.9
S.C. 28.4 26.0 22.0 21.8 16.6 30.6 27.9 25.7 21.2 16.9 32.9 29.8 29.3 20.7 17.3
K.W. 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9
75
T.C. 27.0 29.7 29.6 32.7 33.8 29.1 30.6 31.6 32.6 33.4 31.2 31.5 33.6 32.4 33.0
S.C. 26.9 25.1 21.2 21.1 16.5 29.0 27.2 24.4 21.6 17.2 31.1 29.4 27.5 22.1 17.9
K.W. 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1
85
T.C. 25.4 27.6 27.2 30.7 33.2 27.4 28.5 28.6 31.0 33.2 29.4 29.5 30.0 31.2 33.1
S.C. 25.4 24.1 20.4 20.4 16.5 27.4 26.6 23.1 22.0 17.5 29.4 29.0 25.8 23.6 18.5
K.W. 2.1 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3
95
T.C. 23.9 25.5 24.8 28.6 32.6 25.8 26.5 25.6 29.3 32.9 27.7 27.5 26.5 30.0 33.2
S.C. 23.9 23.2 19.6 19.7 16.4 25.7 25.9 21.8 22.4 17.8 27.6 28.6 24.0 25.0 19.1
K.W. 2.3 2.3 2.3 2.4 2.4 2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.5
105
T.C. 22.5 23.6 22.9 26.2 29.8 24.1 24.6 23.8 26.8 30.1 25.7 25.5 24.6 27.3 30.3
S.C. 22.4 22.1 18.6 18.9 15.4 24.0 24.2 20.9 21.4 16.8 25.6 26.4 23.2 23.9 18.2
K.W. 2.5 2.5 2.5 2.5 2.6 2.5 2.5 2.5 2.6 2.6 2.6 2.6 2.5 2.6 2.6
115
T.C. 21.0 21.8 21.0 23.9 27.1 22.4 22.7 21.9 24.3 27.3 23.8 23.6 22.9 24.7 27.6
S.C. 21.0 21.0 17.6 18.2 14.5 22.3 22.6 20.1 20.5 15.9 23.7 24.2 22.5 22.8 17.2
K.W. 2.6 2.6 2.6 2.7 2.8 2.7 2.7 2.6 2.7 2.8 2.7 2.7 2.7 2.8 2.8
125
T.C. 19.6 19.9 19.1 21.5 24.3 20.7 20.8 20.1 21.8 24.5 21.8 21.7 21.1 22.1 24.8
S.C. 19.5 19.9 16.7 17.4 13.6 20.6 20.9 19.2 19.5 14.9 21.7 22.0 21.7 21.7 16.3
K.W. 2.8 2.8 2.8 2.9 3.0 2.9 2.9 2.8 2.9 3.0 2.9 2.9 2.8 2.9 3.0
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
** For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.
Air Handler Coil
T.C. S.C. KW
MA12B FC/MC35B 1.00 1.00 1.00
MA12B FC/MC42B 1.00 1.00 1.00
AHP30 1.00 0.97 1.00
F*FP040 0.99 0.97 0.99
MV12B* FC/MC35B 1.02 1.00 0.98
MV12B* FC/MC42B 1.02 1.00 0.98
MV16C* FC/MC35C 1.02 1.00 0.98
MV16C* FC/MC42C 1.02 1.00 0.98
AV36* 1.02 1.00 0.98
FC/MC/PC/UC42 1.00 1.00 1.00
HC36 0.99 0.97 0.99
HD36 1.01 1.00 1.01
Variable Speed
Furnace *
Coil
T.C. S.C. KW
(F,L)L8VB16 FC/MC/PC35B 1.02 1.01 0.98
FL9(C,V)B12 FC/MC/PC35B 1.02 1.01 0.98
(F,L)L8VC16 FC/MC/PC35C 1.02 1.00 0.98
FL9(C,V)C16 FC/MC/PC35C 1.02 1.01 0.98
(F,L)L8VB16 FC/MC/PC42B 1.02 1.01 0.98
FL9(C,V)B12 FC/MC/PC42B 1.02 1.01 0.98
(F,L)L8VC16 FC/MC/PC42C 1.02 1.00 0.98
FL9(C,V)C16 FC/MC/PC42C 1.02 1.01 0.98
(F,L)L8VB16 HC36 1.02 1.01 0.98
FL9(C,V)B12 HC36 1.02 1.01 0.98
(F,L)L8VB16 HD36 1.02 1.01 0.98
FL9(C,V)B12 HD36 1.02 1.01 0.98