246819-BTG-H-0208
22 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
* = Single-phase outdoor units only.
* = Single-phase outdoor units only.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. EABD-F042S, EABD-(T,W)042S**
INDOOR COIL MODEL NO. FC/MC/PC/UC48
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 38.3 43.6 41.6 46.5 49.4 40.5 44.8 42.8 47.6 50.2 42.7 46.1 44.0 48.7 50.9
S.C. 38.3 36.8 30.3 31.3 24.1 40.5 39.8 32.7 33.6 25.5 42.7 42.9 35.1 35.8 27.0
K.W. 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.5 2.4 2.4 2.4 2.4 2.5
75
T.C. 37.0 41.4 39.7 44.3 47.0 39.0 42.8 40.8 45.3 47.4 41.0 44.3 41.9 46.3 47.9
S.C. 37.0 35.8 29.5 30.3 23.7 39.0 38.7 31.9 32.6 25.2 41.0 41.5 34.3 34.9 26.7
K.W. 2.6 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.7 2.7 2.6 2.6 2.6 2.7 2.7
85
T.C. 35.6 39.3 37.9 42.1 44.6 37.4 40.9 38.8 43.1 44.7 39.3 42.4 39.7 44.0 44.8
S.C. 35.6 34.8 28.8 29.3 23.4 37.4 37.5 31.1 31.6 24.9 39.3 40.1 33.4 34.0 26.5
K.W. 2.8 2.8 2.8 2.9 2.9 2.8 2.9 2.8 2.9 2.9 2.9 2.9 2.8 2.9 3.0
95
T.C. 34.2 37.2 36.0 40.0 42.2 35.9 38.9 36.8 41.0 42.0 37.6 40.5 37.6 41.6 41.8
S.C. 34.2 33.8 28.0 28.3 23.0 35.9 36.3 30.3 30.8 24.6 37.6 38.8 32.6 33.0 26.3
K.W. 3.0 3.1 3.0 3.1 3.2 3.1 3.1 3.0 3.1 3.2 3.1 3.1 3.1 3.2 3.2
105
T.C. 32.4 35.2 33.6 37.3 39.4 34.2 36.8 34.3 38.0 39.4 36.1 38.4 35.1 38.7 39.4
S.C. 32.4 32.2 26.7 27.1 21.7 34.2 34.3 28.9 29.4 23.3 35.8 36.4 31.2 31.6 24.9
K.W. 3.3 3.3 3.2 3.3 3.4 3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.3 3.4 3.5
115
T.C. 30.6 33.2 31.2 34.7 36.7 32.6 34.7 32.0 35.4 36.9 34.6 36.3 32.7 36.0 37.1
S.C. 30.6 30.6 25.5 26.0 20.5 32.3 32.3 27.6 28.1 22.0 33.7 34.0 29.8 30.2 23.6
K.W. 3.5 3.5 3.5 3.6 3.7 3.5 3.6 3.5 3.6 3.7 3.6 3.6 3.5 3.6 3.7
125
T.C. 28.8 31.2 28.8 32.1 33.9 31.0 32.7 29.6 32.7 34.3 33.1 34.2 30.3 33.3 34.7
S.C. 28.8 29.1 24.3 24.8 19.2 30.3 30.4 26.3 26.8 20.7 31.7 31.7 28.4 28.9 22.2
K.W. 3.7 3.7 3.7 3.8 4.0 3.8 3.8 3.7 3.8 4.0 3.8 3.8 3.7 3.9 4.0
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
** For three-phase, decrease T.C. by 1.0 and S.C. by 0.7.
Air Handler Coil
T.C. S.C. KW
MA14D FC/MC48D 1.00 1.00 1.00
MA16C FC/MC48C 1.00 1.00 1.00
AHP/SHP48 – 1.00 1.00 1.00
MV16C* FC/MC48C 1.00 0.98 1.00
MV20D* FC/MC48D 1.01 0.99 0.97
AV/SV48* – 1.01 0.99 0.97
– HD48 0.99 0.98 0.99
Variable Speed
Furnace *
Coil
T.C. S.C. KW
(F,L)L8VC20 FC/MC/PC48C 1.00 1.00 1.00
FL9(C,V)C16 FC/MC/PC48C 1.00 1.00 1.00
FL9(C,V)C20 FC/MC/PC48C 1.00 1.00 1.00
FL9(C,V)D20 FC/MC/PC48D 1.00 1.00 1.00
(F,L)L8VC20 HD48 0.98 0.98 0.98
FL9(C,V)C16 HD48 0.99 0.99 0.99
FL9(C,V)C20 HD48 0.98 0.98 0.98