York R-410A Air Conditioner User Manual


 
528195-YTG-B-0810
Johnson Controls Unitary Products 23
115°F 125°F
3125
77 139.5 14.4 52.0 44.1 30.8 - - - 131.7 15.8 47.4 40.6 27.0 - - -
72 131.8 14.2 84.1 70.7 57.4 44.1 - - 123.5 15.6 81.4 67.8 54.2 40.6 - -
67 124.1 14.1 116.1 97.4 84.0 70.7 57.4 - 115.3 15.4 115.3 95.0 81.4 67.8 54.2 -
62 118.9 14.0 118.9 117.5 97.0 83.7 70.3 57.0 111.7 15.4 111.7 110.5 89.9 76.4 62.8 49.2
3750
77 143.6 14.4 64.1 48.9 33.7 - - - 135.2 15.8 62.4 45.1 29.5 - - -
72 135.7 14.3 93.3 78.1 62.9 47.6 - - 126.8 15.6 90.4 74.8 59.3 43.7 - -
67 127.8 14.1 122.5 107.2 92.0 76.8 61.6 - 118.4 15.4 118.4 104.6 89.1 73.5 58.0 -
62 122.4 14.0 122.4 121.5 106.2 91.0 75.8 60.6 114.7 15.4 114.7 114.0 98.4 82.9 67.3 51.8
57 120.6 14.1 120.6 120.6 108.1 92.8 77.6 62.4 113.3 15.4 113.3 113.3 101.2 85.6 70.1 54.6
4375
77 147.7 14.5 76.2 53.7 36.6 - - - 138.8 15.8 77.3 49.6 32.1 - - -
72 139.6 14.3 102.5 85.4 68.3 51.2 - - 130.1 15.6 99.4 81.9 64.4 46.9 - -
67 131.5 14.1 128.8 117.1 100.0 82.9 65.8 - 121.5 15.4 121.5 114.2 96.7 79.2 61.7 -
62 125.9 14.1 125.9 125.4 115.4 98.3 81.2 64.1 117.8 15.4 117.8 117.4 106.9 89.4 71.9 54.4
57 124.1 14.1 124.1 124.1 117.4 100.3 83.2 66.1 116.3 15.4 116.3 116.3 109.9 92.4 74.9 57.4
5000
77 151.8 14.5 88.3 58.5 39.5 - - - 142.3 15.9 92.2 54.1 34.6 - - -
72 143.5 14.3 111.7 92.7 73.7 54.8 - - 133.5 15.6 108.4 89.0 69.5 50.0 - -
67 135.1 14.2 135.1 127.0 108.0 89.0 70.0 - 124.6 15.4 124.6 123.8 104.4 84.9 65.5 -
62 129.4 14.1 129.4 129.4 124.6 105.7 86.7 67.7 120.8 15.4 120.8 120.8 115.3 95.9 76.4 57.0
57 127.6 14.1 127.6 127.6 126.8 107.8 88.8 69.8 119.2 15.4 119.2 119.2 118.6 99.1 79.7 60.2
5625
72 147.4 14.4 119.1 98.9 78.8 58.6 - - 137.3 15.7 116.2 95.3 74.5 53.7 - -
67 138.8 14.2 138.8 134.7 115.3 95.2 75.0 - 128.1 15.5 128.1 128.1 111.9 91.0 70.2 -
62 133.0 14.1 133.0 133.0 130.6 110.4 90.2 70.1 124.2 15.5 124.2 124.2 121.5 100.7 79.8 59.0
57 131.0 14.1 131.0 131.0 130.7 110.5 90.3 70.1 122.6 15.5 122.6 122.6 122.3 101.5 80.6 59.8
6250
72 151.3 14.4 126.5 105.2 83.8 62.5 - - 141.1 15.7 123.9 101.7 79.5 57.3 - -
67 142.5 14.2 142.5 142.5 122.7 101.3 80.0 - 131.7 15.5 131.7 131.7 119.4 97.2 74.9 -
62 136.5 14.2 136.5 136.5 136.5 115.2 93.8 72.5 127.6 15.5 127.6 127.6 127.6 105.4 83.2 61.0
57 134.5 14.2 134.5 134.5 134.5 113.2 91.8 70.5 126.0 15.5 126.0 126.0 126.0 103.8 81.6 59.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
XP150 (12.5 Ton) (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65